3. Dedicated input/output signal timing chart
3.1Initial data process for CC-Link connection
c CAUTION
RX (n+7) 8
on
Initial data process request flag
process from the master station |
PLC to the controller must be |
carried out at an interval of |
100ms or more. If the interval is |
RX (n+7) B Remote Ready
off on
off on
too short, the dedicated input may |
not be recognized. (This also |
RYn0:SI(00) Emergency stop input
applies to the same dedicated |
input and differing dedicated |
input intervals.) |
RY(n+1)1:SI(11) Interlock input
off on
• If dedicated outputs are provided |
for the dedicated inputs from the |
RY(n+7)8
off on
5
Specifications
master station PLC to controller, |
use them. |
Initial data process complete flag
off
a) b) c) d) e)
Confirmation of connection with master station PLC at power ON
a)Initial data process request flag ON is output
b)Emergency stop and interlock input ON is input
c)Initial data process complete flag ON is input
d)Initial data process request flag OFF is output
e)Remote Ready ON is output
Connection with the
*This process is always required to correctly connect to the
*To enter the emergency stop state, turn RYn0:SI(00) OFF after the above process is established.
*The servo is OFF when the controller power is turned ON.