3. Dedicated input/output signal timing chart

3.3AUTO mode changeover, program reset and program execution

5

c CAUTION

The dedicated input ON/OFF process from the master station PLC to the controller must be carried out at an interval of 100ms or more. If the interval is too short, the dedicated input may not be recognized. (This also applies to the same dedicated input and differing dedicated input intervals.)

If dedicated outputs are provided for the dedicated inputs from the master station PLC to controller, use them.

on

RXn8:SO(10)

 

AUTO mode status

off

output

on

RXn9:SO(11)

 

Origin return complete

off

status output

on

 

RXnB:SO(13)

 

Robot program execution

off

status output

on

 

RXnC:SO(14)

Program reset status output off

on

RYn9:SI(11)

 

Interlock input

off

 

 

on

RYnA:SI(12)

 

Robot program start input

off

 

 

on

RYnB:SI(13)

 

AUTO mode input

off

 

RYnD:SI(15)

on

 

Program reset input

off

 

a)

b)

c)

d)

e)

f)

g) h) i)

Specifications

100ms or more 100ms or more

AUTO mode changeover process

a)AUTO mode input ON is input

b)AUTO mode status output ON is output

c)After confirming that the AUTO mode status output is ON, the AUTO mode input OFF is input

Program reset process

d)Program reset input ON is input

e)Program reset status output ON is output

f)After confirming that the program reset status output is ON, the program reset input OFF is input

Program execution process

g)Robot program start input ON is input

h)Program reset status output OFF is output

Robot program execution status output ON is output

i)After confirming that the robot program execution status output is ON, the robot program start input OFF is input

*The program cannot be executed if the emergency stop input and interlock input are OFF.

*If the origin return complete status output is not ON, execution of the program may not be possible depending on the execution level setting value.

*When SAFE mode is enabled, dedicated inputs other than SI (00) and SI (11) might be disabled depending on service mode parameter setting unless service mode input signal is set to ON with SI (02) in the CC-Link system.

5-8