Intel 5400 Series manual Mechanical Requirements, Processor Mechanical Parameters

Page 13

Thermal/Mechanical Reference Design

2Thermal/Mechanical Reference Design

This chapter describes the thermal/mechanical reference design for Quad-Core Intel® Xeon® Processor 5400 Series. Both Quad-Core Intel® Xeon® Processor X5400 Series and Quad-Core Intel® Xeon® Processor E5400 Series are targeted for the full range of form factors (2U, 2U+ and 1U). The Quad-Core Intel® Xeon® Processor X5482 sku is an ultra performance version of the Quad-Core Intel® Xeon® Processor 5400 Series with 150W TDP and is use only in workstation platforms.

2.1Mechanical Requirements

The mechanical performance of the processor cooling solution must satisfy the requirements described in this section.

2.1.1Processor Mechanical Parameters

Table 2-1. Processor Mechanical Parameters Table

Parameter

Minimum

Maximum

Unit

Notes

 

 

 

 

 

Volumetric Requirements and Keepouts

 

 

 

1

 

 

 

 

 

Static Compressive Load

 

 

 

3

 

 

 

 

 

Static Board Deflection

 

 

 

3

 

 

 

 

 

Dynamic Compressive Load

 

 

 

3

 

 

 

 

 

Transient Bend

 

 

 

3

 

 

 

 

 

Shear Load

 

70

lbf

2,4,5

 

 

311

N

 

 

 

 

 

 

Tensile Load

 

25

lbf

2,4,6

 

 

111

N

 

 

 

 

 

 

Torsion Load

 

35

in*lbf

2,4,7

 

 

3.95

N*m

 

 

 

 

 

 

Notes:

1.Refer to drawings in Appendix B.

2.In the case of a discrepancy, the most recent Quad-Core Intel® Xeon® Processor 5400 Series Datasheet and LGA771 Socket Mechanical Design Guide supersede targets listed in Table 2-1above.

3.These socket limits are defined in the LGA771 Socket Mechanical Design Guide.

4.These package handling limits are defined in the Quad-Core Intel® Xeon® Processor 5400 Series Datasheet.

5.Shear load that can be applied to the package IHS.

6.Tensile load that can be applied to the package IHS.

7.Torque that can be applied to the package IHS.

Quad-Core Intel® Xeon® Processor 5400 Series TMDG

13

Image 13
Contents Thermal/Mechanical Design Guidelines Quad-Core Intel Xeon Processor 5400 SeriesQuad-Core Intel Xeon Processor 5400 Series Tmdg Contents Figures Preload Test Configuration Tables Initial release of the document Reference Revision Description Date NumberQuad-Core Intel Xeon Processor 5400 Series Tmdg Scope ObjectiveReferences Terms and Descriptions Sheet 1 Definition of TermsTerm Description TDP Terms and Descriptions Sheet 2Introduction Processor Mechanical Parameters Mechanical RequirementsProcessor Mechanical Parameters Table Parameter Minimum Maximum UnitQuad-Core Intel Xeon Processor 5400 Series Package Thermal/Mechanical Reference Design Thermal/Mechanical Reference Design Thermal/Mechanical Reference Design Quad-Core Intel Xeon Processor 5400 Series Considerations Thermal Control Circuit and TDP Processor Thermal Parameters and FeaturesDigital Thermal Sensor Multiple Core Special Considerations Platform Environmental Control Interface PeciMultiple Digital Thermal Sensor Operation PROCHOT#, THERMTRIP#, and FORCEPR# Thermal Monitor for Multiple Core ProductsHeatpipe Orientation for Multiple Core Processors Processor Input Processor OutputFeature Dimension Processor Core Geometric Center DimensionsEquation 2-1.y = ax + b Thermal ProfileEquation 2-2.TCONTROL= -TOFFSET Tcontrol DefinitionTcontrol and Thermal Profile Interaction Thermal Profile B Performance Targets Thermal/Mechanical Reference Design Thermal/Mechanical Reference Design 2U+ CEK, Thermal Profile a Parameter Maximum Unit1U CEK, Thermal Profile B Sea-Level Fan Fail Guidelines1U Alternative Heatsink Fan Speed Control Characterizing Cooling Solution Performance RequirementsFan Speed Control, Tcontrol and DTS Relationship Processor Thermal Characterization Parameter RelationshipsEquation 2-3.ΨCA= Tcase TLA / TDP Condition FSC SchemeEquation 2-4.ΨCA= ΨCS + ΨSA ExampleChassis Thermal Design Capabilities and Improvements Chassis Thermal Design ConsiderationsEquation 2-5.ΨCA= Tcase TLA / TDP = 68 45 / 85 = 0.27 C/W Equation 2-6.ΨSA= ΨCA − ΨCS = 0.27 − 0.05 = 0.22 C/WThermal/Mechanical Reference Design Considerations Heatsink SolutionsHeatsink Design Considerations Summary Thermal Interface MaterialGeometric Envelope Assembly DrawingStructural Considerations of CEK 17 U+ CEK Heatsink Thermal Performance Thermal Solution Performance CharacteristicsEquation 2-8.y = 0.187*X + Thermal Profile AdherenceEquation 2-9.y = 0.246*X + =0.187* X +40Equation 2-10.y = 0.246*X + 1UCEKReference SolutionHeatsink with Captive Screws and Standoffs Components Overview22. Isometric View of the 2U+ CEK Heatsink Recommended Thermal Grease Dispense Weight CEK Heatsink Thermal Mechanical CharacteristicsThermal Interface Material TIM Processor Minimum Maximum Units24. CEK Spring Isometric View CEK SpringThermal/Mechanical Reference Design Fan Specifications Boxed 4-wire PWM/DTS Heatsink Solution Fan Power SupplyDescription Min Typ Max Unit Steady Startup Systems Considerations Associated with the Active CEK Boxed Processor ContentsThermal/Mechanical Reference Design Figure A-1. Isometric View of the 1U Alternative Heatsink Component OverviewThermal Profile Adherence Thermal Solution Performance CharactericsEquation A-1. y = 0.331*x + = Processor power value W 1U Alternative Heatsink Thermal/Mechanical Design Drawing Description Table B-1. Mechanical Drawing ListFigure B-1 2U CEK Heatsink Sheet 1 Figure B-2 2U CEK Heatsink Sheet 2 Figure B-3 U CEK Heatsink Sheet 3 Figure B-4 2U CEK Heatsink Sheet 4 Figure B-5. CEK Spring Sheet 1 Figure B-6. CEK Spring Sheet 2 Figure B-7. CEK Spring Sheet 3 Mechanical Drawings Mechanical Drawings Mechanical Drawings Mechanical Drawings Mechanical Drawings Mechanical Drawings Figure B-14 U CEK Heatsink Sheet 1 Figure B-15 U CEK Heatsink Sheet 2 Figure B-16 U CEK Heatsink Sheet 3 Figure B-17 U CEK Heatsink Sheet 4 Figure B-18. Active CEK Thermal Solution Volumetric Sheet 1 Figure B-19. Active CEK Thermal Solution Volumetric Sheet 2 Figure B-20. Active CEK Thermal Solution Volumetric Sheet 3 Figure B-21 U Alternative Heatsink 1 Figure B-22 U Alternative Heatsink 2 Figure B-23 U Alternative Heatsink 3 Figure B-24 U Alternative Heatsink 4 Mechanical Drawings Test Preparation OverviewHeatsink Preparation Alternate Heatsink Sample Preparation Figure C-3. Preload Test Configuration Time-Zero, Room Temperature Preload Measurement Test Procedure ExamplesTypical Test Equipment Table C-1. Typical Test EquipmentPreload Degradation under Bake Conditions Heatsink Clip Load Methodology Safety Requirements Safety Requirements Structural Reliability Testing Environmental Reliability TestingIntel Verification Criteria for the Reference Designs Reference Heatsink Thermal VerificationPost-Test Pass Criteria 2.2 Recommended Test SequenceTable E-1 Use Conditions Environment Material and Recycling Requirements Recommended BIOS/Processor/Memory Test ProceduresQuality and Reliability Requirements Supplier Information Intel Enabled SuppliersFor 1U Additional Suppliers2U Heatsink Alternative CEK Copper Fin Alternative CEK Copper Fin Enabled Suppliers Information 100 Quad-Core Intel Xeon Processor 5400 Series Tmdg