Emergency Manual Operation
How to power the load from the generator
1.Set the ATS Automatic Operation switch to Disable.
2. Ensure the Source 2 switch is OFF ().
3. At the generator:
a. Set the /Manual/Auto switch on the generator control panel to Manual.
b. Press the Manual Run/Stop button if you need to start the generator.
Pressing this button activates the engine control system and the starting system. The starter will begin cranking and, after a few seconds, the engine should start.
Press
4. Turn the Source 1 switch OFF ():
a. Set the selector on the Source 1 switch to Manual.
The operating lever will swing out when the selector is set to Manual.
b. Turn the Source 1 switch counterclockwise to OFF (). Use the operating lever key for easier operation.
InfraStruXure Power Generation System | 23 |