Emergency Manual Operation
How to return to powering the load from utility
1.Ensure the ATS Automatic Operation switch is set to Disable.
2. Ensure the Source 1 switch is OFF ().
3. Turn the Source 2 switch OFF ():
a. Set the selector on the Source 2 switch to Manual.
The operating lever will swing out when the selector is set to Manual.
b. Turn the Source 2 switch counterclockwise to OFF (). Use the operating lever key for easier operation.
4. Turn the Source 1 switch ON ():
a. Set the selector on the Source 1 switch to Manual.
The operating lever will swing out when the selector is set to Manual.
b. Turn the Source 1 switch clockwise to ON (). Use the operating lever key for easier operation.
c.Close the operating levers on both the Source 1 and Source 2 switches, and then set the selectors back to Auto to lock the switches in place.