How to Connect User Input Contacts and Relay Outputs to the ATS
How to connect contacts to the user interface board
To connect and monitor your contacts:
1.Choose one or more terminals on the user interface board for connecting contacts. The user interface board is connected to the User/EPO port on the ATS monitoring unit.
2.From the ATS display interface:
a.Press ESC or ENTER to go to the
b.Select Config from the
ATS/Voltage Alarms
Generator Config
Testing Help
c. Select Contacts & Relays from the Config menu screen and press ENTER.
System/Network
Contacts & Relays
Electrical Config.
d. Select the type of contact you are connecting: Contact Inputs or Relay Outputs.
Contact Inputs
Relay Outputs
Output Relay Map
You will be prompted for your password to configure these items.
Note
e.Press the Up or Down arrow to select the appropriate contact number and press ENTER.
f.Press the Down arrow to enter a unique Name for the contact and to configure the Normal state of the contact (Open or Closed). The default Normal state is Open. Press ENTER to select the item you wish to configure.
Contact In 02 of 04
Name User Contact 4
Normal: Open
Status: Open
g.Connect contact wires (300
h.Run the wires out the roof of the ATS to your contact’s location.
Ensure the wires are properly retained and kept away from
Caution
62 | InfraStruXure Power Generation System |