ATS/Voltage
S2-Generator
One of the following is displayed to describe the condition of the input from Source 2.
OK | Source 2 is acceptable, as defined in the Transfer Points menu (the generator is |
| running). |
OFF | The generator is not running. |
BAD | Source 2 is not acceptable, as defined in the Transfer Points menu, even though the ATS |
| is commanding the generator to run. |
Press ENTER when the selector arrow rests at the
L1, L2, L3 The Source 2
Frequency The frequency of the Source 2 input, in hertz (Hz).
Qual Describes the quality of the input from Source 2. One of the following conditions is displayed:
•Source Good: The source is acceptable, as defined in the Transfer Points menu.
•Low Voltage: The input voltage is below the configured Low voltage Transfer Point on one or more of the phases.
•High Voltage: The input voltage exceeds the configured High voltage Transfer Point on one or more of the phases.
•Phase Imbalance: The percent voltage difference between two phases, as defined by the Phase Balance setting in the Transfer Points menu, has been exceeded.
•Freq Range: The frequency is outside the configured Freq range, as defined in the Transfer Points menu.
•Bad Rotation: The phase rotation does not match the configured Phase Sequence, as defined in the Transfer Points menu.
Phase Sequence Lists the phase rotation (e.g.,
34 | InfraStruXure Power Generation System |