Teledyne 9060Z manual Operation of the Alarm Relays when an Alarm is Accepted, Function Options

Page 40

Model 9060Z Manual

All of the items in this list are selected as the default setting. Any of these items can be disabled from the common alarm by pressing the ENTER key, and they will then appear on the list in the other alarm relays.

7.2.22 Operation of the Alarm Relays when an Alarm is Accepted

An option is available to in the commissioning menu to change the operation of the alarm relay when an alarm has been accepted. The states for the alarm relay contacts are shown in the following table –

Alarm state

Accepted Relay hold setting‐

Accepted Relay hold setting‐

 

Enabled

Disabled

No alarm condition

Closed circuit

Closed circuit

New alarm

Open circuit

Open circuit

All alarms accepted

Open circuit

Closed circuit

Alarms self cleared

Closed circuit

Closed circuit

The default setting is ‘Enabled’ after a cold start.

7.2.23 Selecting the Correct Fuel

The 9060Z transmitter can calculate several measurements that are based on the oxygen reading and the temperature of the process gas. These calculations also require some details about the chemical makeup of the fuel. The additional calculations are:

 

Oxygen deficiency

 

The volume of oxygen required to bring the combustion back to

 

 

 

 

stoichiometry

 

Combustibles

 

 

This theoretical scale is equivalent to a combustibles analyzer

 

 

Carbon dioxide

The calculated maximum level of CO2 in the combustion gas

 

(maximum dry)

 

 

 

 

Combustion

 

Requires a stack thermocouple and so is only available in single probe

 

efficiency

 

mode

Select the required fuel in function 50 by using the OPTION keys and then press the ENTER key. The table of values in the next 6 functions will be updated for that fuel.

7.2.24 Reference Air Pump Options

Normally the reference air is supplied from the transmitter using the internal pump. The default option is 5.00v.

 

Function

Options

57

Reference Air Pump

External or Internal

58

Internal Pump Voltage

Pump voltage setting, between 2.5 and 5.00 in 0.25v steps

59

Reference Air RH%

If external is selected, set the RH level. (5% if instrument

 

 

air is used)

40

Image 40
Contents Teledyne Analytical Instruments Model 9060Z Manual Keypad Forcing a Cold Start Resetting the Calibration Factors PurgeEmail asktai@teledyne.com Important Notice Regarding 9060 Probe Option ‐ FIL‐3 Important Notices 9060Z Transmitter IntroductionSeries 9060H Oxygen Probes & Sensors Model 9060Z Manual Temperature accuracy Output load Alarm relaysAlarm relay contacts PowerTemperature Range Head TemperatureConnection Weight 9060H 9060UL/UH ApplicationHeated probes‐temperature range 0‐900C 1650F Model 9060Z Manual Function Minimum Maximum Range of outputsInstalling a 9060H Oxygen Probe Installation and CommissioningMounting the Transmitter Oxygen Probe Mounting Installing the Auxiliary Thermocouple 4A Shield Connections4B Earth Connection PE Electrical ConnectionsModel 9060Z Manual Model 9060Z Manual Heater Interlock Relays Connecting AN Oxygen Probe CableHeater Supply Interlock Connection for Heated Probes Model 9060Z Manual Connecting the Auxiliary Thermocouple Optional Connecting the Output ChannelsConnecting the Alarms Connecting the Automatic Purge and Calibration Check SystemConnecting Reference AIR Connecting the Transmitter to a Modbus NetworkOnnecting Power Commissioning ‐ RUN ModeProbe or Sensor Calibration For more details see AppendixCalibration GAS Check Filter PurgingDust in the Flue GAS Connecting a Pressure Transducer StratificationDisplay and Keypad Graphical DisplayKeypad in RUN mode Key text RUN mode White text Setup mode Black textOxygen Display Units KeypadKeypad in Setup / Commissioning / Calibration modes Function up and Function down keys Option up and Option down keysEnter key Probe impedance keySetup Mode Function Summary TableChanging Options Function name RangeProbe 1 Offset Setup Mode FunctionsLower Line Items Oxygen Display Units Process AlarmsDamping Factor Commissioning Mode Model 9060Z Manual Commissioning Mode Functions Model 9060Z Manual Temperature Units Flue Pressure Units and ValueCalibration Freezes Outputs Solenoid 1 & 2 OperationOxygen Content Calibration Gas 1 Maximum Calibration Gas 1 & 2 Positive / Negative ErrorAlarm Relay 1, 2 and 3 Function Common Alarm Relay FunctionOperation of the Alarm Relays when an Alarm is Accepted Selecting the Correct FuelReference Air Pump Options Function OptionsAlarm Log Clearing Communications Port OptionsCalibration Mode Menu Function name RangeCalibration Mode Functions Reference VoltagesHeater SSR Fault Correction Alarms Common AlarmsModel 9060Z Manual Selectable Process Alarms Alarm Relay Options Instrument Calibration Calibration SummaryProbe Calibration Cold StartCalibration GAS GAS Calibration Check and PurgeFunction # Function Description Options Software Upgrades Detailed Fault Analysis TroubleshootingFirst Approach Maintenance Transmitter MaintenanceCleaning Replacement PartsIndex Auxiliary ThermocoupleTroubleshooting Is the H/C atom ratio in the fuel Is the O/C atom ratio in the fuelIs the N/C atom ratio in the fuel Is the S/C atom ratio in the fuelAppendix 2, Probe EMF Tables Zirconia Oxygen Sensor Output mV Probe Type 9060H, SensorProbe EMF Probe EMF @ 720C 1320FZirconia Oxygen Probe Output mV Probe Type 9060UL/UH 13.1 20.726.2 33.8Serial Configuration Modbus ProtocolModel 9060Z Manual Model 9060Z Manual Model 9060Z Manual Model 9060Z Manual Model 9060Z Manual 0x41 Special Instruction Function 0x020x03 0x04