Model 9060Z Manual
0x41 Special Instruction Function
This command allows you to interact with the transmitter allowing access to functionality that would otherwise only be accessible via the keypad. The request length will vary from one command to the next depending on what arguments are required. Requests are formed the same as other modbus requests:
1 byte | 1 byte | 1 byte | 0 ‐4 bytes | 2 bytes |
slave address | command code | function code | arguments | checksum |
Function Code | Command | Arguments |
0x01 | Accept All Active Alarms | none |
0x02 | remote set key down | 1 byte keymask |
0x03 | remote reset key down | 1 byte keymask |
0x04 | Initiate Probe Impedance Check | none |
0x05 | Set Internal Clock | 4 byte rtc* |
* date expressed as seconds since 1‐Jan 2004
67