Model 9060Z Manual
7.2.25 Communications Port Options
The 9060Z transmitter has a serial communications port available at terminals 18 to 22. The default protocol is for RS‐232 running at 19,200 baud rate with 8 bits, Even parity and 1 stop bit.
|
|
| Function |
|
| Options |
|
|
|
| |||
60 |
|
| Serial Interface |
|
| RS‐232 or RS‐485 (Use RS‐485 for MODBUS) |
|
|
| ||||
61 |
|
| Serial Baud Rate |
| 9600, 19200, 38400, 57600 (RS‐232 up to 19200 only) | |
62 |
|
| Serial Parity |
|
| Even, Odd or No Parity |
63 |
|
| MODBUS |
| Set the MODBUS address for this device between 1 and 246. | |
| Address |
| 0 is to disable the MODBUS |
7.2.26 Alarm Log Clearing
Every alarm that is instigated internally in the transmitter or as a process level is recorded in the alarm log with the activation time, accepted time and the cleared time. The last 4000 events will be recorded and then the oldest alarms will be dropped off as new ones occur. If you would like to delete the log recording select CLEAR in SETUP step 64 by using the OPTION keys and press the ENTER key. The message “Alarm Log Cleared” will be displayed.