Teledyne 9060Z Connecting the Auxiliary Thermocouple Optional, Connecting the Output Channels

Page 22

Model 9060Z Manual

4.8 CONNECTING THE AUXILIARY THERMOCOUPLE (OPTIONAL)

For 9060H heated probes, the auxiliary thermocouple must be a separate TC with the junction isolated from earth, mounted near to and upstream of the oxygen probe. It can be either a K, J, R or S type thermocouple. It is optional. If the auxiliary temperature or combustion efficiency is not to be displayed or transmitted, then an auxiliary thermocouple is not necessary. The thermocouple should be connected to terminals 7 & 8. These terminals will not be available for an auxiliary thermocouple if a second probe has been installed.

4.9 CONNECTING THE OUTPUT CHANNELS

The two 4 to 20 mA DC output channels are capable of driving into a 1000Ω load. The output terminals are 12 & 13 for channel 1, and 14 & 15 for channel 2.

4.10 CONNECTING THE ALARMS

A common alarm, which should be connected for all installations initiates on alarm functions described below. Three additional alarm relays are available for selectable functions as listed in chapter 9.2. Each relay has normally open contacts. The contacts will open in alarm condition. Relays are connected as follows:

Relay Common Alarm

Terminal Numbers 26 & 27

 

Alarm 1

 

28 & 29

 

Alarm 2

 

30 & 31

 

Alarm 3

 

32 & 33

 

Common Alarms All of the following conditions will cause a common alarm ‐

Probe 1

(2)

Heater Fail

Ref Air Pump Fail

Heater 1 (2) SSR Failure

Probe 1

(2)

High Impedance

ADC Calibration Fail

Heater SSR Leakage

Probe 1

(2)

TC Open Circuit

Alarm Log Fail

Probe 1 (2) Filter Blocked

Aux TC Open Circuit

Output 1 (2) Failure

Gas 1 (2) Calibration Error

 

 

 

 

BBRAM Fail

The watchdog timer is a special alarm. There will not be an alarm message displayed, but the transmitter will reset.

Alarms can be accepted by pressing the alarm button (viewing the alarm messages).

Alarm relay 2 to 4 Select any one or all of the following for each relay. Refer chapter 9.

In addition, any of the selections that are removed from the common alarm relay can be added to relays two to four.

High oxygen 1 (2)

Probe 1

(2) temperature low

Low oxygen 1 (2)

Calibration check 1 (2) in progress

Very low oxygen 1 (2)

Probe 1

(2) purge in progress

Oxygen deviation

 

 

4.11 CONNECTING THE AUTOMATIC PURGE AND CALIBRATION CHECK SYSTEM

CAUTION

The purge and calibration solenoid valves are supplied with mains voltage. This supply has electrical shock danger to maintenance personnel. Always isolate the transmitter before working with the purge and calibration solenoid valves.

22

Image 22
Contents Teledyne Analytical Instruments Model 9060Z Manual Keypad Forcing a Cold Start Resetting the Calibration Factors PurgeEmail asktai@teledyne.com Important Notice Regarding 9060 Probe Option ‐ FIL‐3 Important Notices 9060Z Transmitter IntroductionSeries 9060H Oxygen Probes & Sensors Model 9060Z Manual Alarm relay contacts Temperature accuracyOutput load Alarm relays PowerConnection Weight Temperature RangeHead Temperature 9060H 9060UL/UH ApplicationHeated probes‐temperature range 0‐900C 1650F Model 9060Z Manual Function Minimum Maximum Range of outputsInstalling a 9060H Oxygen Probe Installation and CommissioningMounting the Transmitter Oxygen Probe Mounting 4B Earth Connection PE Installing the Auxiliary Thermocouple4A Shield Connections Electrical ConnectionsModel 9060Z Manual Model 9060Z Manual Heater Interlock Relays Connecting AN Oxygen Probe CableHeater Supply Interlock Connection for Heated Probes Model 9060Z Manual Connecting the Alarms Connecting the Auxiliary Thermocouple OptionalConnecting the Output Channels Connecting the Automatic Purge and Calibration Check SystemConnecting Reference AIR Connecting the Transmitter to a Modbus NetworkProbe or Sensor Calibration Onnecting PowerCommissioning ‐ RUN Mode For more details see AppendixCalibration GAS Check Filter PurgingDust in the Flue GAS Connecting a Pressure Transducer StratificationDisplay and Keypad Graphical DisplayOxygen Display Units Keypad in RUN modeKey text RUN mode White text Setup mode Black text KeypadKeypad in Setup / Commissioning / Calibration modes Enter key Function up and Function down keysOption up and Option down keys Probe impedance keyChanging Options Setup ModeFunction Summary Table Function name RangeProbe 1 Offset Setup Mode FunctionsLower Line Items Oxygen Display Units Process AlarmsDamping Factor Commissioning Mode Model 9060Z Manual Commissioning Mode Functions Model 9060Z Manual Calibration Freezes Outputs Temperature UnitsFlue Pressure Units and Value Solenoid 1 & 2 OperationAlarm Relay 1, 2 and 3 Function Oxygen Content Calibration Gas 1Maximum Calibration Gas 1 & 2 Positive / Negative Error Common Alarm Relay FunctionReference Air Pump Options Operation of the Alarm Relays when an Alarm is AcceptedSelecting the Correct Fuel Function OptionsAlarm Log Clearing Communications Port OptionsCalibration Mode Menu Function name RangeCalibration Mode Functions Reference VoltagesHeater SSR Fault Correction Alarms Common AlarmsModel 9060Z Manual Selectable Process Alarms Alarm Relay Options Instrument Calibration Calibration SummaryProbe Calibration Cold StartCalibration GAS GAS Calibration Check and PurgeFunction # Function Description Options Software Upgrades Detailed Fault Analysis TroubleshootingFirst Approach Cleaning MaintenanceTransmitter Maintenance Replacement PartsIndex Auxiliary ThermocoupleTroubleshooting Is the N/C atom ratio in the fuel Is the H/C atom ratio in the fuelIs the O/C atom ratio in the fuel Is the S/C atom ratio in the fuelProbe EMF Appendix 2, Probe EMF TablesZirconia Oxygen Sensor Output mV Probe Type 9060H, Sensor Probe EMF @ 720C 1320FZirconia Oxygen Probe Output mV Probe Type 9060UL/UH 26.2 13.120.7 33.8Serial Configuration Modbus ProtocolModel 9060Z Manual Model 9060Z Manual Model 9060Z Manual Model 9060Z Manual Model 9060Z Manual 0x03 0x41 Special Instruction Function0x02 0x04