English
GROUNDING INSTRUCTIONS
IN THE EVENT OF A MALFUNCTION OR BREAKDOWN, grounding provides a path of least resistance for electric current and reduces the risk of shock. This tool is equipped with an electric cord that has an equipment grounding conductor and grounding plug. The plug MUST be plugged into a matching receptacle that is properly installed and grounded in accordance with ALL local codes and ordinances.
DO NOT MODIFY THE PLUG PROVIDED. If it will not fit the receptacle, have the proper receptacle installed by a qualified electrician.
IMPROPER CONNECTION of the equipment grounding conductor can result in risk of electric shock. The conductor with the green insulation (with or without yellow stripes) is the equipment grounding conductor. If repair or replacement of the electric cord or plug is necessary, DO NOT connect the equipment grounding conductor to a live terminal.
CHECK with a qualified electrician or service personnel if you do not completely understand the grounding instructions, or if you are not sure the tool is properly grounded.
USE ONLY
FIGURE A shows a 3-prong electrical plug and receptacle that has a grounding conductor. If a properly grounded receptacle is not available, an adapter (FIGURE B) can be used to temporarily connect this plug to a 2-contact ungrounded receptacle. The adapter (FIGURE B) has a rigid lug extending from it that MUST be connected to a permanent earth ground, such as a properly grounded receptacle box. THE TEMPORARY ADAPTER SHOULD BE
USED ONLY UNTIL A PROPER GROUNDED OUTLET CAN BE INSTALLED BY A QUALIFIED ELECTRICIAN. The Canadian Electrical Code prohibits the use of adapters.
CAUTION: In all cases, make certain the receptacle in question is properly grounded. If you are not sure have a certified electrician check the receptacle.
WARNING
This drill press is for indoor use only. Do not expose to rain or use in damp locations.
Fig. A
Grounding Prong
Propely Grounded
GUIDELINES FOR EXTENSION CORDS
Make sure your extension cord is in good condition. When using an extension cord, be sure to use one heavy enough to carry the current your product will draw. An undersized cord will cause a drop in line voltage resulting in loss of power and overheating. The table below shows the correct size to use according to cord length and nameplate ampere rating. If in doubt, use the next heavier gauge. The smaller the gauge number, the heavier the cord.
Fig. B
Grounding Lug
Adapter
Make Sure This is Connected to a Known Ground
Be sure your extension cord is properly wired and in good condition. Always replace a damaged extension cord or have it repaired by a qualified person before using it. Protect your extension cords from sharp objects, excessive heat and damp or wet areas.
Use a separate electrical circuit for your tools. This circuit must not be less than #12 wire and should be protected with a 15 Amp time lag fuse. Before connecting the motor to the power line, make sure the switch is in the OFF position and the electric current is rated the same as the current stamped on the motor nameplate. Running at a lower voltage will damage the motor.
This tool is intended for use on a circuit that has a receptacle like the one illustrated in FIGURE A.
WARNING
This tool must be grounded while in use to protect the operator from electrical.
MINMUN GAUGE FOR EXTENSION CORDS (AWG)
(When using 120 volts only)
Ampere Rating | Total length of cord in feet | |||||
|
|
|
|
|
|
|
| not |
|
|
|
|
|
more than | more than | 25' | 50' | 100' |
| 150' |
|
|
|
|
|
|
|
0 | 6 | 18 | 16 | 16 |
| 14 |
|
|
|
|
|
|
|
6 | 10 | 18 | 16 | 14 |
| 12 |
|
|
|
|
|
|
|
10 | 12 | 16 | 16 | 14 |
| 12 |
|
|
|
|
|
|
|
|
|
|
|
| Not | |
12 | 16 | 14 | 12 | recommended |
SAVE THESE INSTRUCTIONS
— 6 —