Recommended equipment for on-site analysis includes a thermometer, pH meter, and dissolved oxygen meter. Dissolved oxygen and temperature must be measured on-site and it is recommended that pH be measured on-site. All other analyses should be performed by a professional water quality analyst. The Langelier Index (Ll) is calculated using the following equation and the tables found on the following pages.

Ll = pH - (9.30 + Total Dissolved Solids chart value + Temperature chart value ) + Hardness chart valve + Alkalinity chart value)

The Ll is zero when the water is in chemical balance. If the Ll is greater than zero, there is a tendency to form scale. If the Ll is less than zero, the water tends to be corrosive.

Dissolved oxygen may be controlled in closed cooling towers. Several types of treatments are commercially available to remove dissolved oxygen. For open cooling towers, dissolved oxygen is not an easily controlled parameter. Also, a filtration system is recommended for the water going into the air compressor when using an open cooling tower.

It should be noted that Ingersoll-Rand’s guidelines and recommendations should be used in evaluating the water systems and the problems that may occur in the normal operation of our air compressors. If water problems persist or are not covered above, you should consult a professional.

86

Image 88
Contents Phone CCN 80440415 REV B Form Apdd 738BAIR Compressor Group Bonded Warranty & Registered Start UP Rotary Screw AIR Compressor This unit was purchased fromTable of Contents Safety and Warnings Safety Shutdown Lift Here DecalsDecals Viewed From RearCompressor Package Data Inspection Ingersoll-Rand Company Davidson, North CarolinaUnpacking and Handling ToolsVentilation Foundation RequirementsNever elevate the compressor unit Performance will be affectedMoisture Content of Compressed AIR PipingDo not use the compressor to support the discharge pipe Discharge Piping with Aftercooler ROTARY-RECIP in ParallelElectrical Installation Rotary TWO Compressor SystemRotation Check Drive MotorElectrical Installation Hasp Lever TAG KEY LockFAN Motor Intellisys Operating InstructionsOutdoor Sheltered Installation 1 Typical Outdoor Sheltered Installation Intellisys Intellisys ControllerPower on Light Intellisys Controls Emergency StopStart StopCurrent Status Display ScreenCurrent Status Items Diagram OperatorPanel Flow Figure IntellisysMain Menu Operator SetpointsOptions Options Items Range Step UnitOptions Sensor Calibration Alarm HistorySensor Calibration Items Alarm History Items Clock FunctionsIntegral Sequencing Integral Sequencing Range Step UnitStatus Main Menu Reset Alarms Alarm Main MenuPage Maintenance Schedule Maintenance RecordsMaintenance Procedures Number of Running HOURS, Whichever Occurs FirstInlet AIR Filter Coolant Filter200 HP/132-160 KW Requires 2 Elements ElementsCoolant Items RequiredCoolant Drain Hot coolant can cause severe injuryCoolant ProcedureSeparator Tank Scavenge SCREEN/ORIFICE Tools Required Coolant Separator Element Tank cover bolt torque valuesRecommended Bolt Tightening Cross Pattern 125/200 HPCooler Cores Cleaning Coolant CoolersAftercooler Aftercooler CleaningAftercooler Motor Lubrication Relubrication amount Lubricant Amount Motor Frame Size GramsMotor Bearing Maintenance Stored Units Motor LubricationRecommended Motor Grease Hazardous voltage. Can cause severe injury or deathLong Term Storage General Intellisys RemovalTools Controller RemovalInstallation Coolant Sampling ProcedureCoolant Hoses RemovalAIR Cooled Compressors Design Temperatures General System InformationCoolant Cooler Cooling FAN MotorCompressed AIR System The air system is composed COOLANT/AIR Separation SystemOperation Electrical SystemSTAR-DELTA Type Starter Stepper Motor Inlet ControlCapacity Control Automatic Unloaded StartAutomatic START/STOP Control Modulation onlyFirst Some Examples of Operation SecondExample Remote START/STOP Troubleshooting Chart Troubleshooting Chart Power Outage Restart Option SequencerLOW Ambient Separator DELTA-P SolenoidRemote LOAD/UNLOAD ModbusElectrical Schematic Star Delta Reference DrawingsPage Foundation Plan 125-150 HP/90-110KW Aircooled Single Stage Foundation Plan 125-150 HP/90-110 KW Aircooled Single Stage Foundation Plan 200 HP/132-160 KW Aircooled Single Stage Foundation Plan 200 HP/132-160 KW Aircooled Single Stage REV C REV C Foundation Plan 200 HP/132-160 KW Watercooled Single Stage Foundation Plan 200 HP/132-160 KW Watercooled Single Stage Foundation Plan Aircooled 100-150 HP/75-110 KW TWO StageFoundation Plan Aircooled 100-150 HP/75-110 KW TWO Stage Foundation Plan Aircooled 200 HP/132-160 KW TWO Stage Foundation Plan Aircooled 200 HP/132-160 KW TWO Stage Foundation Plan -WATERCOOLED Foundation Plan -WATERCOOLED 100-150 HP/75-110 KW TWO Stage Foundation Plan -WATERCOOLED 200 HP/132-160 KW TWO Stage Foundation Plan -WATERCOOLED 200 HP/132-160 KW TWO Stage Flow Schematic Aircooled Single Stage Page Flow Schematic Watercooled 90F 32C Single Stage Page Flow Schematic Watercooled 115F 46 Single Stage Page Flow Schematic AIR-COOLED TWO Stage Page Flow Schematic Watercooled 90F 32C TWO Stage Page Flow Schematic Watercooled 115F 46C TWO Stage Page Typical System Flow Diagram Typical System Flow DiagramsTypical System Flow Diagrams Typical System Flow Diagrams Typical System Flow Diagrams Typical System Flow Diagrams Scale CorrosionFouling Parameter Concentration Frequency of AnalysisPage Temperature F Total dissolved solids ppmHardness ppm Alkalinity ppmMaintenance Record Maintenance Record Maintenance Record Maintenance Record