3.6 OPTIONS (CONTINUED)

3.6.1Auto Restart- This setpoint is used to enable or disable the auto restart option.

3.6.2Auto Restart Time- This setpoint is the minimum time period the compressor must run unloaded before it can stop in the auto restart mode.

3.6.3Auto Restart Delay Time- If the compressor is stopped in auto restart, this setpoint is the number of seconds the package discharge pressure must remain below the online pressure setpoint before the compressor will restart.

3.6.4Sequencer- This setpoint is used to enable or disable sequencer operation.

3.6.5Remote Start/Stpop- This setpoint is used to enable or disable the remote start/stop option.

3.6.6Power Out Restart- This setpoint is used to enable or disable the power out restart option, if it is installed.

3.7.7Power Out Restart Time- If the power out restart option is installed and enabled, this setpoint is time period between power returning to the compressor and the compressor starting.

3.6.8Low Ambient- This setpoint enables or disables the low ambient option. If the low ambient option is enabled, sensor 3CTT must be installed in the compressor.

3.6.9Minimum Cooler Out Temperature- When the low ambient option is installed, this setpoint is the minimum temperature to which the coolant must rise before the compressor will load.

3.6.10Separator Delta-P Solenoid- This setpoint enables or disables the separator delta-p solenoid option. Enabling this option will automatically disable the Separator Delta-P Sensor option.

3.6.11Separator Delta-P Sensor- This setpoint enables or disables the separator delta-p sensor option. Enabling this option will automatically disable the Separator Delta-P Solenoid option.

3.6.12Lead/Lag Cycle Length- This setpoint enables the automatic cycling between lead and lag operation. If it is set to a value greater than 0, the controller will cycle between lead and lag operation. The value of this set point is the cycle length in real time hours. A value of 0 will disable the automatic cycling between lead and lag.

3.6.13Scheduled Start- If the scheduled start/stop option is installed, this set point is the time of the day (hour and minute) that the compressor will automatically start. To disable this option, set it to the same value as the scheduled stop (section 3.6.14).

3.6.14Scheduled Stop- If the scheduled start/stop option is installed, this setpoint is the time of the day (hour and minute) that the compressor will automatically stop. To disable this option, set it to the same value as the scheduled start (section 3.6.13).

3.6.15High Dust Filter- This option enables or disables the high dust filter operation.

3.6.16Modbus Protocol- This option is for Ingersoll- Rand service use only.

3.6.17Modbus Address- This feature is used with the Modbus Protocol and is for Ingersoll-Rand service use only.

22

Image 24
Contents Phone CCN 80440415 REV B Form Apdd 738BAIR Compressor Group Bonded Warranty & Registered Start UP Rotary Screw AIR Compressor This unit was purchased fromTable of Contents Safety and Warnings Safety Shutdown Lift Here DecalsDecals Viewed From RearCompressor Package Data Inspection Ingersoll-Rand Company Davidson, North CarolinaUnpacking and Handling ToolsVentilation Foundation RequirementsNever elevate the compressor unit Performance will be affectedMoisture Content of Compressed AIR PipingDo not use the compressor to support the discharge pipe Discharge Piping with Aftercooler ROTARY-RECIP in ParallelElectrical Installation Rotary TWO Compressor SystemRotation Check Drive MotorElectrical Installation Hasp Lever TAG KEY LockFAN Motor Intellisys Operating InstructionsOutdoor Sheltered Installation 1 Typical Outdoor Sheltered Installation Intellisys Intellisys ControllerPower on Light Intellisys Controls Emergency StopStart StopDisplay Screen Current StatusCurrent Status Items Diagram OperatorPanel Flow Figure IntellisysMain Menu Operator SetpointsOptions Options Items Range Step UnitOptions Alarm History Sensor CalibrationSensor Calibration Items Alarm History Items Clock FunctionsIntegral Sequencing Integral Sequencing Range Step UnitStatus Main Menu Reset Alarms Alarm Main MenuPage Maintenance Schedule Maintenance RecordsMaintenance Procedures Number of Running HOURS, Whichever Occurs FirstInlet AIR Filter Coolant Filter200 HP/132-160 KW Requires 2 Elements ElementsCoolant Items RequiredCoolant Drain Hot coolant can cause severe injuryProcedure CoolantSeparator Tank Scavenge SCREEN/ORIFICE Tools Required Coolant Separator Element Tank cover bolt torque valuesRecommended Bolt Tightening Cross Pattern 125/200 HPCooler Cores Cleaning Coolant CoolersAftercooler Cleaning AftercoolerAftercooler Motor Lubrication Relubrication amount Lubricant Amount Motor Frame Size GramsMotor Bearing Maintenance Stored Units Motor LubricationRecommended Motor Grease Hazardous voltage. Can cause severe injury or deathLong Term Storage General Intellisys RemovalTools Controller RemovalInstallation Coolant Sampling ProcedureCoolant Hoses RemovalAIR Cooled Compressors Design Temperatures General System InformationCoolant Cooler Cooling FAN MotorCompressed AIR System The air system is composed COOLANT/AIR Separation SystemOperation Electrical SystemSTAR-DELTA Type Starter Stepper Motor Inlet ControlCapacity Control Automatic Unloaded StartModulation only Automatic START/STOP ControlFirst Second Some Examples of OperationExample Remote START/STOP Troubleshooting Chart Troubleshooting Chart Power Outage Restart Option SequencerLOW Ambient Separator DELTA-P SolenoidRemote LOAD/UNLOAD ModbusElectrical Schematic Star Delta Reference DrawingsPage Foundation Plan 125-150 HP/90-110KW Aircooled Single Stage Foundation Plan 125-150 HP/90-110 KW Aircooled Single Stage Foundation Plan 200 HP/132-160 KW Aircooled Single Stage Foundation Plan 200 HP/132-160 KW Aircooled Single Stage REV C REV C Foundation Plan 200 HP/132-160 KW Watercooled Single Stage Foundation Plan 200 HP/132-160 KW Watercooled Single Stage Foundation Plan Aircooled 100-150 HP/75-110 KW TWO StageFoundation Plan Aircooled 100-150 HP/75-110 KW TWO Stage Foundation Plan Aircooled 200 HP/132-160 KW TWO Stage Foundation Plan Aircooled 200 HP/132-160 KW TWO Stage Foundation Plan -WATERCOOLED Foundation Plan -WATERCOOLED 100-150 HP/75-110 KW TWO Stage Foundation Plan -WATERCOOLED 200 HP/132-160 KW TWO Stage Foundation Plan -WATERCOOLED 200 HP/132-160 KW TWO Stage Flow Schematic Aircooled Single Stage Page Flow Schematic Watercooled 90F 32C Single Stage Page Flow Schematic Watercooled 115F 46 Single Stage Page Flow Schematic AIR-COOLED TWO Stage Page Flow Schematic Watercooled 90F 32C TWO Stage Page Flow Schematic Watercooled 115F 46C TWO Stage Page Typical System Flow Diagram Typical System Flow DiagramsTypical System Flow Diagrams Typical System Flow Diagrams Typical System Flow Diagrams Typical System Flow Diagrams Scale CorrosionFouling Parameter Concentration Frequency of AnalysisPage Temperature F Total dissolved solids ppmHardness ppm Alkalinity ppmMaintenance Record Maintenance Record Maintenance Record Maintenance Record