Ingersoll-Rand 125-200 HP/90-160 KW Modulation only, Automatic START/STOP Control, First

Page 45

5.8 CAPACITY CONTROL (Continued)

MODULATION/ACS CONTROL (Continued)

The automatic control selector (ACS) is designed to continuously monitor the plant air demand and select either the on-off line, or the modulate control mode - whichever is most desirable at any time during an operating day.

It allows the compressor to operate in its most efficient mode without attendance, thereby reducing power costs to a minimum.

When the compressor operates in the on-off line control mode, the length of time the compressor remains in the “off line” condition is an indication of the plant air demand. Intellisys controller is sensing and awaiting a sufficient line pressure decrease before signaling a shift to the on line mode. If the “off line” time period is relatively short, thereby indicating a high demand for air, it is preferable to shift the control system to upper range modulation.

The Intellisys does this, and does it automatically if the compressor unloads 3 times within a 3 minute time period.

If later, the plant demand decreases, and even under modulate control the line pressure reaches the setting of the Intellisys controller and the control shifts to the “off line” mode, the time in this mode will still be monitored. A long “off line” time period indicates a low plant air demand, indicating the desirability of operating in the on-off line mode.

The Intellisys then does this, and does it automatically if the compressor operates unloaded for more than 3 minutes.

MODULATION ONLY

If MODULATION ONLY is turned on in the set point routine, the unit will shift to Modulation control mode immediately when the unit is running. The 3 cycles within 3 minutes time period required for ACS to change to Modulation mode is bypassed. The unit will stay in Modulation mode until the UNLOAD button is pressed or the Mode of Operation set point is changed.

5.9 AUTOMATIC START/STOP CONTROL

Many plant air systems have widely varying air demands or large air storage capacity which allows for automatic standby air capacity control.

During periods of low air demand, if the line pressure rises to the upper set point, the Intellisys begins to time out. If the line pressure remains above the lower set point for as long as the set time, the compressor will stop. At the same time the display will indicate the compressor has shut down automatically and will restart automatically. An automatic restart will occur when the line pressure drops to the lower set point.

The upper and lower set points and shutdown delay time are set on the Intellisys control panel. There is a 10 second delay after shutdown during which the compressor will not restart even if line air pressure drops below the lower set point. This is to allow the motor to come to a complete stop and the Intellisys controller to collect current data of operating condition. If line air pressure is below the lower set point at the end of 10 seconds, the unit will start unless the load delay timer is set greater than 10 seconds.

Auto Restart Delay

This is the number of seconds the line pressure must remain below the online set point before the compressor will start if it was stopped due to an auto start/stop situation. This timer will not delay an auto restart if the time is set to 0.

Automatic Start/Stop Operation

When in operation, the compressor must meet two specific timing intervals before the Intellisys controller will stop the unit in an Automatic Start/Stop situation.

For this discussion, the timers will be called timer “A” and timer “B”.

FIRST

Timer “A” prevents the compressor from automatically starting more than 6 times an hour by requiring the unit to run at least 10 minutes after each automatic start.

This 10 minute run period can be loaded, unloaded or a combination of the two and allows dissipation of heat generated within the motor windings at start.

43

Image 45
Contents Form Apdd 738B Phone CCN 80440415 REV BAIR Compressor Group Bonded Warranty & Registered Start UP This unit was purchased from Rotary Screw AIR CompressorTable of Contents Safety and Warnings Safety Shutdown Decals Lift HereViewed From Rear DecalsCompressor Package Data Ingersoll-Rand Company Davidson, North Carolina InspectionUnpacking and Handling ToolsFoundation Requirements VentilationNever elevate the compressor unit Performance will be affectedPiping Moisture Content of Compressed AIRDo not use the compressor to support the discharge pipe Discharge Piping with Aftercooler ROTARY-RECIP in ParallelRotary TWO Compressor System Electrical InstallationDrive Motor Rotation CheckHasp Lever TAG KEY Lock Electrical InstallationFAN Motor Intellisys Operating InstructionsOutdoor Sheltered Installation 1 Typical Outdoor Sheltered Installation Intellisys Controller IntellisysIntellisys Controls Emergency Stop Power on LightStart StopDisplay Screen Current StatusCurrent Status Items Operator DiagramPanel Flow Figure IntellisysOperator Setpoints Main MenuOptions Items Range Step Unit OptionsOptions Alarm History Sensor CalibrationSensor Calibration Items Clock Functions Alarm History ItemsIntegral Sequencing Range Step Unit Integral SequencingStatus Main Menu Reset Alarm Main Menu AlarmsPage Maintenance Records Maintenance ScheduleMaintenance Procedures Number of Running HOURS, Whichever Occurs FirstCoolant Filter Inlet AIR Filter200 HP/132-160 KW Requires 2 Elements ElementsItems Required CoolantCoolant Drain Hot coolant can cause severe injuryProcedure CoolantSeparator Tank Scavenge SCREEN/ORIFICE Tools Required Tank cover bolt torque values Coolant Separator ElementRecommended Bolt Tightening Cross Pattern 125/200 HPCoolant Coolers Cooler Cores CleaningAftercooler Cleaning AftercoolerAftercooler Relubrication amount Lubricant Amount Motor Frame Size Grams Motor LubricationMotor Lubrication Motor Bearing Maintenance Stored UnitsRecommended Motor Grease Hazardous voltage. Can cause severe injury or deathIntellisys Removal Long Term Storage GeneralTools Controller RemovalCoolant Sampling Procedure InstallationCoolant Hoses RemovalGeneral System Information AIR Cooled Compressors Design TemperaturesCoolant Cooler Cooling FAN MotorCOOLANT/AIR Separation System Compressed AIR System The air system is composedOperation Electrical SystemStepper Motor Inlet Control STAR-DELTA Type StarterCapacity Control Automatic Unloaded StartModulation only Automatic START/STOP ControlFirst Second Some Examples of OperationExample Remote START/STOP Troubleshooting Chart Troubleshooting Chart Sequencer Power Outage Restart OptionLOW Ambient Separator DELTA-P SolenoidModbus Remote LOAD/UNLOADReference Drawings Electrical Schematic Star DeltaPage Foundation Plan 125-150 HP/90-110KW Aircooled Single Stage Foundation Plan 125-150 HP/90-110 KW Aircooled Single Stage Foundation Plan 200 HP/132-160 KW Aircooled Single Stage Foundation Plan 200 HP/132-160 KW Aircooled Single Stage REV C REV C Foundation Plan 200 HP/132-160 KW Watercooled Single Stage Foundation Plan 200 HP/132-160 KW Watercooled Single Stage 100-150 HP/75-110 KW TWO Stage Foundation Plan AircooledFoundation Plan Aircooled 100-150 HP/75-110 KW TWO Stage Foundation Plan Aircooled 200 HP/132-160 KW TWO Stage Foundation Plan Aircooled 200 HP/132-160 KW TWO Stage Foundation Plan -WATERCOOLED Foundation Plan -WATERCOOLED 100-150 HP/75-110 KW TWO Stage Foundation Plan -WATERCOOLED 200 HP/132-160 KW TWO Stage Foundation Plan -WATERCOOLED 200 HP/132-160 KW TWO Stage Flow Schematic Aircooled Single Stage Page Flow Schematic Watercooled 90F 32C Single Stage Page Flow Schematic Watercooled 115F 46 Single Stage Page Flow Schematic AIR-COOLED TWO Stage Page Flow Schematic Watercooled 90F 32C TWO Stage Page Flow Schematic Watercooled 115F 46C TWO Stage Page Typical System Flow Diagrams Typical System Flow DiagramTypical System Flow Diagrams Typical System Flow Diagrams Typical System Flow Diagrams Typical System Flow Diagrams Corrosion ScaleFouling Parameter Concentration Frequency of AnalysisPage Total dissolved solids ppm Temperature FHardness ppm Alkalinity ppmMaintenance Record Maintenance Record Maintenance Record Maintenance Record