Page 48

Temperatures Menu (cont)

 

 

 

 

Description/Action

Display

 

Tank Temperature - non adjustable - control system

Top of Menu

 

 

sensed temperature (averaged from upper and lower

Temperatures

 

 

temperature probes).

Operating Set Point

 

140°F

Upper Temperature - non adjustable - control system

 

Differential

 

8°F

 

sensed temperature from the Upper Temperature Probe.

 

Lower Temperature - non adjustable - control system

Tank Temperature

 

120°F

Upper Temperature

 

122°F

 

sensed temperature from the Lower Temperature Probe.

 

(Heater Regulated to Tank) - non adjustable -

Lower Temperature

 

118°F

(Heater Regulated to Tank)

 

 

configuration information.

 

Upper Probe & Lower Probe Offset - adjustable user

Upper Probe Offset

 

0°F

 

setting, range -5° to +5° (factory setting 0°).

CHANGE

BACK

HELP

 

Note: These settings should only be used if the hot water

 

 

 

 

 

supply temperature varies greatly from the Operating Set

Bottom of Menu

 

 

Point setting.

 

 

The Upper and Lower Probe Offsets are used to calibrate

Temperatures

 

 

control system temperature sensing. This can improve the

Differential

 

8°F

 

precision of temperature control in the storage tank and at

 

 

Tank Temperature

 

120°F

 

points of use. This feature can also be used to compensate

 

 

Upper Temperature

 

122°F

 

for building recirculation loops (hot water returning to the

 

 

Lower Temperature

 

118°F

 

storage tank) that may cause the heating cycles to terminate

 

 

prematurely.

(Heater Regulated to Tank)

 

 

Example: If the current sensed temperature from a

Upper Probe Offset

 

0°F

 

Lower Probe Offset

 

0°F

 

temperature probe is 120°F (49°C) and the Offset setting for

 

 

that probe is adjusted to a value other than 0°, the control

CHANGE

BACK

HELP

 

system would calibrate or “offset” the sensed temperature

 

 

 

 

 

from the probe and the averaged tank temperature. Heating

 

 

 

 

cycles would be activated and deactivated based on the

 

 

 

 

calibrated (offset) temperature.

 

 

 

These settings are adjusted in the same way described for the Operating Set Point And Differential Adjustment on page 47.

Heater Status Menu

 

Description/Action

Display

 

Select Heater Status from the Main Menu and press the

Top of Menu

 

Operational Button under "SELECT" to enter this menu. This

Heater Status

 

menu contains non adjustable operational information. Use the

Status

Standby

Up & Down Buttons to navigate the menu.

Status - displays the current Operating State, see Table 12

ECO Contact

Closed

Low Gas PS

Closed

 

on page 46.

ECO Contact, Low Gas PS, Blocked Inlet PS, Blocked

Blocked Inlet PS

Closed

Blocked Outlet PS

Closed

 

Outlet PS, Blower Prover PS - displays the current state

 

of the switch contacts; open or closed.

Blower Prover PS

Open

Blower On, Igniter On, Gas Valve On - displays whether

Blower On

No

 

or not the control system is currently energizing these water

BACK

HELP

 

heater components; yes = energized, no = de-energized.

 

 

 

Igniter Current - displays whether or not the control

Bottom of Menu

 

 

system has detected the required minimum current, see

 

 

Sequence Of Operation on page 58.

Heater Status

 

Flame Detected - displays whether or not the control

Blower On

No

 

system has detected Main Burner flame during ignition from

 

Igniter On

No

 

the flame sensor.

External Input Enable - displays whether or not the S1

Igniter Current

No

Gas Valve On

No

 

dipswitches have been configured to activate the enable/

 

disable circuit, see Enable/Disable Circuit on page 41.

Flame Detected

No

Ignition Trials - displays whether or not the S1 dipswitches

External Input Enable

No

 

have been configured to allow 1 or 3 trials for ignition

Ignition Trials

3

 

before declaring an "Ignition Failure" Fault condition, see

BACK

HELP

 

the CCB - Central Control Board Layout on page 67.

 

 

 

48

Image 48
Contents Commercial gas water heaters Table Of Contents Safe Installation, Use and Service ApprovalsGeneral Safety Information PrecautionsHydrogen Gas Flammable Overheated water can cause water tank explosionInstalling, using or servicing Water heater Fire or Explosion HazardFire and Explosion Hazard Preparing For The Installation IntroductionAbbreviations Used QualificationsFeatures And Components Basic OperationWater Heater’s 120 VAC on/off switch Top Views 120,000 & 150,000SUF 120 & 150 Components Top Views SUF 199 & 250 ComponentsWater heaters 24 Volt Gas Valve Left Side Right Side Installation Considerations Rough In DimensionsTOP Views Recovery Capacities Locating The Water HeaterGas Line Connection Size Storage CapacitiesExtended Vent Terminations Optional Concentric TerminationsHard Water Circulation PumpsInstallation Requirements Power SupplyGas Pressure Requirements Supply Gas LineMixing Valves Dishwashing MachinesClosed Water Systems Thermal ExpansionTemperature-Pressure Relief Valve Water Damage HazardValve Discharge Pipe Requirements Condensate Drain Combustible Material StorageContaminated Air Condensate Drain Water TrapBreathing Hazard Carbon Monoxide Gas Air RequirementsUnconfined Space Confined SpaceFresh Air Openings For Confined Spaces Outdoor Air Through Two OpeningsOutdoor Air Through One Opening Outdoor Air Through Two Horizontal DuctsPage Commonwealth of Massachusetts InspectionVenting Installation General Venting InformationGeneral Venting Instructions SUF 199 & SUF 250 Intake Air Connection Correct OrientationLarge Hose Fernco Clamp TEE FittingVenting Requirements Venting Installation Sequence Power Vent InstallationDirect Vent Installation Intake AIR Screen Field SuppliedVertical Termination Installation Standard Factory Supplied TerminationsMaximum Factory Supplied Standard Termination Field Supplied STRAP/SUPPORTIntake AIR AND/OR Vent Exhaust Sidewall Termination Installation Concentric Termination Installation Determine the location for the terminationInch Concentric Termination Installation Inch Concentric Termination KITTWO Concentric Terminations Three Concentric TerminationsFour Concentric Terminations Eight Concentric TerminationsMultiple Concentric Termination Arrangements Two Concentric TerminationsEight Concentric Terminations Sidewall RoofPower Vent Horizontal Venting ArrangementsDirect Vent Horizontal Direct Vent Vertical Vent Horizontal Intake Direct Vent Horizontal Vent Vertical IntakeDirect Vent Horizontal Concentric Termination Clearances Sidewall Power Vent Power VentTermination Clearances Sidewall Direct Vent Direct VentWater Heater Installation Condensate Drain InstallationInstallation Notes Installation InstructionsSupply Gas Line Installation Gas Line SizingSupply Gas Line Sizing U. S. Units Supply Gas Line Sizing Metric UnitsSupply Gas Regulator Installation Gas Line Leak TestingGas Line Connection Electrical Wiring Power Supply ConnectionsEnable/Disable Circuit Connecting An External Supervisory ControlWater Piping Diagrams Water Line ConnectionsValve Discharge Pipe Thermometers not SuppliedTemperature Regulation High Temperature Limit Control ECOHigh Temperature Applications Thermostat ControlTank Temperature 103F Operating Set Point 120F Control System OperationOverview Control System NavigationStatus Icons Icon DescriptionOperating States State DescriptionControl System Menus Menu DescriptionUser Settings & Control System Menus Update CancelBack Help Description/Action DisplayChange Back Help Display Settings Description/Action Heater Information Description/Action DisplayBack Advanced View Back HelpECO YESUpdate Service Contact InformationSelect Back Help NameStart Up Prior to Start upInitial Start Up GAS Valve / Venturi Assembly TOP View GAS Valve TOP Detail ViewLighting The Water Heater Gas pressure reading while the water heater is firingMultiple Appliance Installations High Altitude Installations Checking The Firing Rate1050 = 300,000 Btu/hr 87.9 kW To Turn Off GasLighting The Water Heater SUF 60 120 and SUF 100 150 Models onlyLighting & Operation Labels Tank Temperature 103F Operating Set Point 120F SUF 100 199 and SUF 100 250 Models onlyTroubleshooting Installation ChecklistSequence Of Operation Sequence Of Operation Flow Chart Closed by control system Fault Msg is displayedPre-Purge cycle Operational Problems Installation ErrorsRough Starting, Rough Operation Momentary IgnitionFault And Alert Conditions Fault And Alert Messages Possible Causes Check/Repair Displayed Fault/Alert MessageBack Advanced Blower Prover Failure No Anode VoltageMaintenance Maintenance ScheduleGeneral Draining And FlushingFilling The Water Heater Sediment RemovalLime Scale Removal Manual Lime Scale RemovalPowered Anode Rods Drain Valve and Access PanelsTemperature-Pressure Relief Valve Test Vent SystemDiagrams J3 J5J10 J13 J11 CCB Central Control Board LayoutSUF 120 & 150 Wiring Diagram User Interface ModulSUF 199 & 250 Wiring Diagram CCB Central Control BoardCirculation Pump Wiring Diagrams Water Piping Diagrams Temperature & Pressure Tank Temperature ALT. Cold Water State Storage Tank Water Piping Diagrams Line Temperature Control HOT Water Outlet Pipe T&P to Open Drain Finished Floor Limited Warranty