Franklin 2007 manual 150, 200 250, 260, 280, 290, 440 540, 370 460 560, 460 570, 420 510 630

Page 22

Application – Three-Phase Motors

Table 19 Three-Phase 75 °C Cable, 60 Hz (Service Entrance to Motor) Maximum Length in Feet

75 °C

MOTOR RATING

 

 

 

 

 

75 °C INSULATION - AWG COPPER WIRE SIZE

 

 

 

 

 

MCM COPPER WIRE SIZE

 

VOLTS

HP

KW

14

12

10

8

6

4

3

2

1

 

0

00

000

0000

250

300

350

400

500

 

1/2

0.37

710

1140

1800

2840

 

4420

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4

0.55

510

810

1280

2030

 

3160

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

0.75

430

690

1080

1710

 

2670

4140

5140

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

1.1

310

500

790

1260

 

1960

3050

3780

 

 

 

 

 

 

 

 

 

 

 

 

200 V

2

1.5

240

390

610

970

 

1520

2360

2940

3610

4430

 

5420

 

 

 

 

 

 

 

 

3

2.2

180

290

470

740

 

1160

1810

2250

2760

3390

 

4130

 

 

 

 

 

 

 

 

60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Three-

5

3.7

170

280

440

 

690

1080

1350

1660

2040

 

2490

3050

3670

4440

5030

 

 

 

 

Phase

7.5

5.5

0

0

200

310

 

490

770

960

1180

1450

 

1770

2170

2600

3150

3560

 

 

 

 

3 - Lead

 

 

 

 

 

 

10

7.5

0

0

150

230

 

370

570

720

880

1090

 

1330

1640

1970

2390

2720

3100

3480

3800

4420

 

 

 

 

15

11

0

0

0

160

 

250

390

490

600

740

 

910

1110

1340

1630

1850

2100

2350

2570

2980

 

20

15

0

0

0

0

 

190

300

380

460

570

 

700

860

1050

1270

1440

1650

1850

2020

2360

 

25

18.5

0

0

0

0

 

0

240

300

370

460

 

570

700

840

1030

1170

1330

1500

1640

1900

 

30

22

0

0

0

0

 

0

200

250

310

380

 

470

580

700

850

970

1110

1250

1360

1590

 

1/2

0.37

930

1490

2350

3700

 

5760

8910

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4

0.55

670

1080

1700

2580

 

4190

6490

8060

9860

 

 

 

 

 

 

 

 

 

 

 

 

1

0.75

560

910

1430

2260

 

3520

5460

6780

8290

 

 

 

 

 

 

 

 

 

 

 

 

1.5

1.1

420

670

1060

1670

 

2610

4050

5030

6160

7530

 

9170

 

 

 

 

 

 

 

 

230 V

2

1.5

320

510

810

1280

 

2010

3130

3890

4770

5860

 

7170

8780

 

 

 

 

 

 

 

3

2.2

240

390

620

990

 

1540

2400

2980

3660

4480

 

5470

6690

8020

9680

 

 

 

 

 

60 Hz

 

 

 

 

 

 

 

 

 

140

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Three-

5

3.7

230

370

590

 

920

1430

1790

2190

2690

 

3290

4030

4850

5870

6650

7560

8460

9220

 

Phase

7.5

5.5

0

160

260

420

 

650

1020

1270

1560

1920

 

2340

2870

3440

4160

4710

5340

5970

6500

7510

3 - Lead

 

 

10

7.5

0

0

190

310

 

490

760

950

1170

1440

 

1760

2160

2610

3160

3590

4100

4600

5020

5840

 

 

 

 

15

11

0

0

0

210

 

330

520

650

800

980

 

1200

1470

1780

2150

2440

2780

3110

3400

3940

 

20

15

0

0

0

160

 

250

400

500

610

760

 

930

1140

1380

1680

1910

2180

2450

2680

3120

 

25

18.5

0

0

0

0

 

200

320

400

500

610

 

750

920

1120

1360

1540

1760

1980

2160

2520

 

30

22

0

0

0

0

 

0

260

330

410

510

 

620

760

930

1130

1280

1470

1650

1800

2110

 

1/2

0.37

2690

4290

6730

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4

0.55

2000

3190

5010

7860

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

0.75

1620

2580

4060

6390

 

9980

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

1.1

1230

1970

3100

4890

 

7630

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

1.5

870

1390

2180

3450

 

5400

8380

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

2.2

680

1090

1710

2690

 

4200

6500

8020

9830

 

 

 

 

 

 

 

 

 

 

 

 

5

3.7

400

640

1010

1590

 

2490

3870

4780

5870

7230

 

8830

 

 

 

 

 

 

 

 

 

7.5

5.5

270

440

690

1090

 

1710

2640

3260

4000

4930

 

6010

7290

8780

 

 

 

 

 

 

 

10

7.5

200

320

510

800

 

1250

1930

2380

2910

3570

 

4330

5230

6260

7390

8280

9340

 

 

 

380 V

15

11

0

0

370

590

 

920

1430

1770

2170

2690

 

3290

4000

4840

5770

6520

7430

8250

8990

 

60 Hz

20

15

0

0

280

440

 

700

1090

1350

1670

2060

 

2530

3090

3760

4500

5110

2840

6510

7120

8190

Three-

25

18.5

0

0

0

360

 

570

880

1100

1350

1670

 

2050

2510

3040

3640

4130

4720

5250

5740

6590

Phase

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 - Lead

30

22

0

0

0

290

 

470

730

910

1120

1380

 

1700

2080

2520

3020

3430

3920

4360

4770

5490

 

40

30

0

0

0

0

 

0

530

660

820

1010

 

1240

1520

1840

2200

2500

2850

3170

3470

3990

 

50

37

0

0

0

0

 

0

440

540

660

820

 

1000

1220

1480

1770

2010

2290

2550

2780

3190

 

60

45

0

0

0

0

 

0

370

460

560

690

 

850

1030

1250

1500

1700

1940

2150

2350

2700

 

75

55

0

0

0

0

 

0

0

0

460

570

 

700

860

1050

1270

1440

1660

1850

2030

2350

 

100

75

0

0

0

0

 

0

0

0

0

420

 

510

630

760

910

1030

1180

1310

1430

1650

 

125

90

0

0

0

0

 

0

0

0

0

0

 

0

510

620

740

840

950

1060

1160

1330

 

150

110

0

0

0

0

 

0

0

0

0

0

 

0

0

520

620

700

790

880

960

1090

 

175

130

0

0

0

0

 

0

0

0

0

0

 

0

0

0

560

650

750

840

920

1070

 

200

150

0

0

0

0

 

0

0

0

0

0

 

0

0

0

0

550

630

700

760

880

Lengths in BOLD only meet the US National Electrical Code ampacity requirements for individual conductors in free air or water. Lengths NOT in bold meet NEC ampacity requirements for either individual conductors or jacketed cable. See page 11 for additional details.

19

Continued on page 20

Image 22
Contents Submersible Motors Important Information for Installers of this Equipment Commitment to Quality Page Application Installation Maintenance Manual Submersible MotorsFrequency of Starts Application All MotorsStorage Mounting PositionTransformer Capacity Transformer Capacity Single-Phase or Three-PhaseEffects of Torque Torque Required ExamplesEngine Driven Generators Use of Engine Driven Generators Single-Phase or Three-PhaseUse of Check Valves KVARequired Cooling Flow Water Temperature and FlowFlow Inducer Sleeve MotorHead Loss in Feet Meters at Various Flow Rates Head Loss From Flow Past MotorHot Water Applications Standard Motors Minimum gpm l/m Required for 3 ft/s .91 m/sec Flow RateHot Water Applications Example Service Factor HorsepowerMaximum Water Temperature Heat Factor Multiplier at 3 ft/s .91 m/sec Flow RateGrounding Surge Arrestors Drawdown SealsGrounding Control Boxes and Panels Control Box and Panel EnvironmentWire Motor Solid State Controls Application Single-Phase MotorsWire Control Boxes QD Relays Solid State200 120180 250Two or More Different Cable Sizes Can Be Used Actual Length FormulaSingle-Phase Motor Specifications 60 Hz 3450 rpm Single-Phase Motor Fuse Sizing Buck-Boost Transformers Auxiliary Running CapacitorsBuck-Boost Transformer Sizing Application Three-Phase Motors Three-Phase 60 C Cable 250 400 140 220150 240 450260 150200 250 280Three-Phase 75 C Cable 340 420 120 180130 340 400 490Amps Watts Three-Phase Motor Specifications 60 HzFull Load Maximum Efficiency % Locked Rotor AmpsThree-Phase Motor Fuse Sizing 575KW Volts Amps Watts Efficiency %100 150 200 175 250 225 125 110 300 17.5 Rating Full Load Maximum Efficiency Locked Rotor AmpsDual Element Overload Relays 60 Hz 4 MotorsHeaters for Furnas60 Hz 6 Motors Nema Heaters for AdjustableFootnotes for Tables 28, 29, Submersible Pump Installation Check List Date Filled In By Motor PumpControl Panel Power SupplyTransformers Incoming VoltageInstallation Controls and Protective DevicesVoltage To Motor Insulation CheckAmps To Motor Recommended Adjustable Overload Relays 60 Hz 8 MotorsKVAR Required 60 Hz SubMonitor Three-Phase ProtectionPower Factor Correction Motor Kvar Required for PFThree-Phase Starter Diagrams Line Voltage ControlThree-Phase Power Unbalance Checking and Correcting Rotation and Current UnbalanceThree-Phase Motor Lead Identification Phase ConvertersReduced Voltage Starters Inline Booster Pump SystemsFeed Water Temperature C AIR Franklin Cable chart See 12. WiringSource of Cable Ampacity Availability Variable Speed Submersible Pump Operation, Inverter Drives Installation All Motors Dimensions Standard Water WellShaft Height and Free End Play Tightening Motor Lead Connector Jam NutPump to Motor Coupling Submersible Leads and CablesMotor Does Not Start Maintenance All MotorsSystem Troubleshooting Motor Starts Too OftenMotor Runs Continuously Motor Runs But Overload Protector TripsPreliminary Tests All Sizes Single- and Three-Phase ResistanceResistance of Drop Cable ohms Insulation Resistance ReadingsNormal ohm and Megohm Values Between All Leads and Ground Single-Phase Control Boxes Checking and Repairing Procedures Power OnQD, Solid State Control Box Power Off Ohmmeter TestsOverload Kits 60 Hz QD Relay Replacement Kits QD Capacitor Replacement KitsQD Control Box Parts 60 Hz Control BOX Model no Capacitors MFD Volts Integral Horsepower Control Box Parts 60 HzOverload Relay Integral hp Voltage Relay Replacement Kits Integral hp Capacitor Replacement KitsIntegral hp Overload Replacement Kits Integral hp Contactor Replacement KitsControl Box Wiring Diagrams 1 hp QD RelayHp Standard Hp Deluxe 282 201 Hp X-LARGE Pumptec-Plus Maintenance Electronic ProductsPumptec-Plus Troubleshooting During Installation Unit Appears DeadPumptec-Plus Troubleshooting After Installation QD Pumptec & Pumptec Troubleshooting QD Pumptec and PumptecSubDrive/MonoDrive Troubleshooting SubDrive75, 150, 300, MonoDrive, & MonoDrive XTSubMonitor Troubleshooting SubMonitorSubtrol-Plus Obsolete See SubMonitor Subtrol-Plus Troubleshooting After InstallationGreen Off Time Light on Abbreviations IgbtPage Page Page Toll Free Help from a Friend