Application – All Motors
Storage
Franklin Electric submersible motors are a water- lubricated design. The fi ll solution consists of a mixture of deionized water and Propylene Glycol (a
but no damage occurs. Repeated freezing and thawing should be avoided to prevent possible loss of fi ll solution.
There may be an interchange of fi ll solution with well water during operation. Care must be taken with motors removed from wells during freezing conditions to prevent damage.
When the storage temperature does not exceed
100 °F (37 °C), storage time should be limited to two years. Where temperatures reach 100° to 130 °F, storage time should be limited to one year.
Loss of a few drops of liquid will not damage the motor as an excess amount is provided, and the fi lter check valve will allow lost liquid to be replaced by fi ltered well water upon installation. If there is reason to believe there has been a considerable amount of leakage, consult the factory for checking procedures.
Frequency of Starts
The average number of starts per day over a period of months or years infl uences the life of a submersible pumping system. Excessive cycling affects the life of control components such as pressure switches, starters, relays and capacitors. Rapid cycling can also cause motor spline damage, bearing damage, and motor overheating. All these conditions can lead to reduced motor life.
The pump size, tank size and other controls should be selected to keep the starts per day as low as practical for longest life. The maximum number of starts per
Motors should run a minimum of one minute to dissipate heat build up from starting current. 6" and larger motors should have a minimum of 15 minutes between starts or starting attempts.
Mounting Position
Table 3 Number of Starts
MOTOR RATING | MAXIMUM STARTS PER 24 HR PERIOD | ||
HP | KW | ||
Up to 0.75 | Up to 0.55 | 300 | 300 |
1 thru 5.5 | 0.75 thru 4 | 100 | 300 |
7.5 thru 30 | 5.5 thru 22 | 50 | 100 |
40 and over | 30 and over | - | 100 |
|
|
|
|
Franklin submersible motors are designed primarily for operation in the vertical,
During acceleration, the pump thrust increases as its output head increases. In cases where the pump head stays below its normal operating range during startup and full speed condition, the pump may create upward thrust. This creates upward thrust on the motor upthrust bearing. This is an acceptable operation for short periods at each start, but running continuously with upthrust will cause excessive wear on the upthrust bearing.
With certain additional restrictions as listed in this section and the Inline Booster Pump Systems sections of this manual, motors are also suitable for operation in positions
from
1.Minimize the frequency of starts, preferably to fewer than 10 per
2.Do not use in systems which can run even for short periods at full speed without thrust toward the motor.
3