Franklin 2007 manual Application All Motors, Storage, Frequency of Starts, Mounting Position

Page 6

Application – All Motors

Storage

Franklin Electric submersible motors are a water- lubricated design. The fi ll solution consists of a mixture of deionized water and Propylene Glycol (a non-toxic antifreeze). The solution will prevent damage from freezing in temperatures to -40 °F (-40 °C); motors should be stored in areas that do not go below this temperature. The solution will partially freeze below 27 °F (-3 °C),

but no damage occurs. Repeated freezing and thawing should be avoided to prevent possible loss of fi ll solution.

There may be an interchange of fi ll solution with well water during operation. Care must be taken with motors removed from wells during freezing conditions to prevent damage.

When the storage temperature does not exceed

100 °F (37 °C), storage time should be limited to two years. Where temperatures reach 100° to 130 °F, storage time should be limited to one year.

Loss of a few drops of liquid will not damage the motor as an excess amount is provided, and the fi lter check valve will allow lost liquid to be replaced by fi ltered well water upon installation. If there is reason to believe there has been a considerable amount of leakage, consult the factory for checking procedures.

Frequency of Starts

The average number of starts per day over a period of months or years infl uences the life of a submersible pumping system. Excessive cycling affects the life of control components such as pressure switches, starters, relays and capacitors. Rapid cycling can also cause motor spline damage, bearing damage, and motor overheating. All these conditions can lead to reduced motor life.

The pump size, tank size and other controls should be selected to keep the starts per day as low as practical for longest life. The maximum number of starts per 24-hour period is shown in table 3.

Motors should run a minimum of one minute to dissipate heat build up from starting current. 6" and larger motors should have a minimum of 15 minutes between starts or starting attempts.

Mounting Position

Table 3 Number of Starts

MOTOR RATING

MAXIMUM STARTS PER 24 HR PERIOD

HP

KW

SINGLE-PHASE

THREE-PHASE

Up to 0.75

Up to 0.55

300

300

1 thru 5.5

0.75 thru 4

100

300

7.5 thru 30

5.5 thru 22

50

100

40 and over

30 and over

-

100

 

 

 

 

Franklin submersible motors are designed primarily for operation in the vertical, shaft-up position.

During acceleration, the pump thrust increases as its output head increases. In cases where the pump head stays below its normal operating range during startup and full speed condition, the pump may create upward thrust. This creates upward thrust on the motor upthrust bearing. This is an acceptable operation for short periods at each start, but running continuously with upthrust will cause excessive wear on the upthrust bearing.

With certain additional restrictions as listed in this section and the Inline Booster Pump Systems sections of this manual, motors are also suitable for operation in positions

from shaft-up to shaft-horizontal. As the mounting position becomes further from vertical and closer to horizontal, the probability of shortened thrust bearing life increases. For normal motor life expectancy with motor positions other than shaft-up, follow these recommendations:

1.Minimize the frequency of starts, preferably to fewer than 10 per 24-hour period. 6” and 8” motors should have a minimum of 20 minutes between starts or starting attempts

2.Do not use in systems which can run even for short periods at full speed without thrust toward the motor.

3

Image 6
Contents Submersible Motors Important Information for Installers of this Equipment Commitment to Quality Page Application Installation Maintenance Manual Submersible MotorsFrequency of Starts Application All MotorsStorage Mounting PositionTransformer Capacity Transformer Capacity Single-Phase or Three-PhaseEffects of Torque Torque Required ExamplesEngine Driven Generators Use of Engine Driven Generators Single-Phase or Three-PhaseUse of Check Valves KVARequired Cooling Flow Water Temperature and FlowFlow Inducer Sleeve MotorHead Loss in Feet Meters at Various Flow Rates Head Loss From Flow Past MotorHot Water Applications Standard Motors Minimum gpm l/m Required for 3 ft/s .91 m/sec Flow RateHot Water Applications Example Service Factor HorsepowerMaximum Water Temperature Heat Factor Multiplier at 3 ft/s .91 m/sec Flow RateGrounding Surge Arrestors Drawdown SealsGrounding Control Boxes and Panels Control Box and Panel EnvironmentWire Motor Solid State Controls Application Single-Phase MotorsWire Control Boxes QD Relays Solid State200 120180 250Two or More Different Cable Sizes Can Be Used Actual Length FormulaSingle-Phase Motor Specifications 60 Hz 3450 rpm Single-Phase Motor Fuse Sizing Auxiliary Running Capacitors Buck-Boost TransformersBuck-Boost Transformer Sizing Application Three-Phase Motors Three-Phase 60 C Cable 250 400 140 220150 240 450260 150200 250 280Three-Phase 75 C Cable 340 420 120 180130 340 400 490Amps Watts Three-Phase Motor Specifications 60 HzFull Load Maximum Efficiency % Locked Rotor AmpsThree-Phase Motor Fuse Sizing 575KW Volts Amps Watts Efficiency %100 150 200 175 250 225 125 110 300 17.5 Rating Full Load Maximum Efficiency Locked Rotor AmpsDual Element Overload Relays 60 Hz 4 MotorsHeaters for FurnasNema Heaters for Adjustable 60 Hz 6 MotorsFootnotes for Tables 28, 29, Submersible Pump Installation Check List Date Filled In By Motor PumpControl Panel Power SupplyTransformers Incoming VoltageInstallation Controls and Protective DevicesInsulation Check Voltage To MotorAmps To Motor Recommended Adjustable Overload Relays 60 Hz 8 MotorsKVAR Required 60 Hz SubMonitor Three-Phase ProtectionPower Factor Correction Motor Kvar Required for PFThree-Phase Starter Diagrams Line Voltage ControlThree-Phase Power Unbalance Checking and Correcting Rotation and Current UnbalanceThree-Phase Motor Lead Identification Phase ConvertersReduced Voltage Starters Inline Booster Pump SystemsFeed Water Temperature C Franklin Cable chart See 12. Wiring AIRSource of Cable Ampacity Availability Variable Speed Submersible Pump Operation, Inverter Drives Installation All Motors Dimensions Standard Water WellShaft Height and Free End Play Tightening Motor Lead Connector Jam NutPump to Motor Coupling Submersible Leads and CablesMotor Does Not Start Maintenance All MotorsSystem Troubleshooting Motor Starts Too OftenMotor Runs Continuously Motor Runs But Overload Protector TripsPreliminary Tests All Sizes Single- and Three-Phase ResistanceInsulation Resistance Readings Resistance of Drop Cable ohmsNormal ohm and Megohm Values Between All Leads and Ground Single-Phase Control Boxes Checking and Repairing Procedures Power OnQD, Solid State Control Box Power Off Ohmmeter TestsQD Capacitor Replacement Kits Overload Kits 60 Hz QD Relay Replacement KitsQD Control Box Parts 60 Hz Integral Horsepower Control Box Parts 60 Hz Control BOX Model no Capacitors MFD VoltsOverload Relay Integral hp Voltage Relay Replacement Kits Integral hp Capacitor Replacement KitsIntegral hp Overload Replacement Kits Integral hp Contactor Replacement KitsControl Box Wiring Diagrams 1 hp QD RelayHp Standard Hp Deluxe 282 201 Hp X-LARGE Pumptec-Plus Maintenance Electronic ProductsPumptec-Plus Troubleshooting During Installation Unit Appears DeadPumptec-Plus Troubleshooting After Installation QD Pumptec & Pumptec Troubleshooting QD Pumptec and PumptecSubDrive/MonoDrive Troubleshooting SubDrive75, 150, 300, MonoDrive, & MonoDrive XTSubMonitor Troubleshooting SubMonitorSubtrol-Plus Troubleshooting After Installation Subtrol-Plus Obsolete See SubMonitorGreen Off Time Light on Abbreviations IgbtPage Page Page Toll Free Help from a Friend