Franklin 2007 manual Application Three-Phase Motors

Page 19

Application – Three-Phase Motors

Table 16 Three-Phase 60 °C Cable, 60 Hz (Service Entrance to Motor) Maximum Length in Feet

60 °C

MOTOR RATING

 

 

 

 

60 °C INSULATION - AWG COPPER WIRE SIZE

 

 

 

 

MCM COPPER WIRE SIZE

 

VOLTS

HP

KW

14

12

10

8

6

4

3

2

1

0

00

000

0000

250

300

350

400

500

 

1/2

0.37

710

1140

1800

2840

4420

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4

0.55

510

810

1280

2030

3160

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

0.75

430

690

1080

1710

2670

4140

5140

 

 

 

 

 

 

 

 

 

 

 

 

1.5

1.1

310

500

790

1260

1960

3050

3780

 

 

 

 

 

 

 

 

 

 

 

200 V

2

1.5

240

390

610

970

1520

2360

2940

3610

4430

5420

 

 

 

 

 

 

 

 

3

2.2

180

290

470

740

1160

1810

2250

2760

3390

4130

 

 

 

 

 

 

 

 

60 Hz

 

 

 

 

 

 

 

 

 

 

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Three-

5

3.7

170

280

440

690

1080

1350

1660

2040

2490

3050

3670

4440

5030

 

 

 

 

Phase

7.5

5.5

0

0

200

310

490

770

960

1180

1450

1770

2170

2600

3150

3560

 

 

 

 

3 - Lead

 

 

 

 

10

7.5

0

0

0

230

370

570

720

880

1090

1330

1640

1970

2390

2720

3100

3480

3800

4420

 

 

15

11

0

0

0

160

250

390

490

600

740

910

1110

1340

1630

1850

2100

2350

2570

2980

 

20

15

0

0

0

0

190

300

380

460

570

700

860

1050

1270

1440

1650

1850

2020

2360

 

25

18.5

0

0

0

0

0

240

300

370

460

570

700

840

1030

1170

1330

1500

1640

1900

 

30

22

0

0

0

0

0

0

250

310

380

470

580

700

850

970

1110

1250

1360

1590

 

1/2

0.37

930

1490

2350

3700

5760

8910

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4

0.55

670

1080

1700

2580

4190

6490

8060

9860

 

 

 

 

 

 

 

 

 

 

 

1

0.75

560

910

1430

2260

3520

5460

6780

8290

 

 

 

 

 

 

 

 

 

 

 

1.5

1.1

420

670

1060

1670

2610

4050

5030

6160

7530

9170

 

 

 

 

 

 

 

 

230 V

2

1.5

320

510

810

1280

2010

3130

3890

4770

5860

7170

8780

 

 

 

 

 

 

 

3

2.2

240

390

620

990

1540

2400

2980

3660

4480

5470

6690

8020

9680

 

 

 

 

 

60 Hz

 

 

 

 

 

 

 

140

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Three-

5

3.7

230

370

590

920

1430

1790

2190

2690

3290

4030

4850

5870

6650

7560

8460

9220

 

Phase

7.5

5.5

0

160

260

420

650

1020

1270

1560

1920

2340

2870

3440

4160

4710

5340

5970

6500

7510

3 - Lead

10

7.5

0

0

190

310

490

760

950

1170

1440

1760

2160

2610

3160

3590

4100

4600

5020

5840

 

 

15

11

0

0

0

210

330

520

650

800

980

1200

1470

1780

2150

2440

2780

3110

3400

3940

 

20

15

0

0

0

0

250

400

500

610

760

930

1140

1380

1680

1910

2180

2450

2680

3120

 

25

18.5

0

0

0

0

0

320

400

500

610

750

920

1120

1360

1540

1760

1980

2160

2520

 

30

22

0

0

0

0

0

260

330

410

510

620

760

930

1130

1280

1470

1650

1800

2110

 

1/2

0.37

2690

4290

6730

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4

0.55

2000

3190

5010

7860

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

0.75

1620

2580

4060

6390

9980

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

1.1

1230

1970

3100

4890

7630

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

1.5

870

1390

2180

3450

5400

8380

 

 

 

 

 

 

 

 

 

 

 

 

 

3

2.2

680

1090

1710

2690

4200

6500

8020

9830

 

 

 

 

 

 

 

 

 

 

 

5

3.7

400

640

1010

1590

2490

3870

4780

5870

7230

8830

 

 

 

 

 

 

 

 

 

7.5

5.5

270

440

690

1090

1710

2640

3260

4000

4930

6010

7290

8780

 

 

 

 

 

 

 

10

7.5

200

320

510

800

1250

1930

2380

2910

3570

4330

5230

6260

7390

8280

9340

 

 

 

380 V

15

11

0

0

370

590

920

1430

1770

2170

2690

3290

4000

4840

5770

6520

7430

8250

8990

 

60 Hz

20

15

0

0

0

440

700

1090

1350

1670

2060

2530

3090

3760

4500

5110

5840

6510

7120

8190

Three-

25

18.5

0

0

0

360

570

880

1100

1350

1670

2050

2510

3040

3640

4130

4720

5250

5740

6590

Phase

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 - Lead

30

22

0

0

0

0

470

730

910

1120

1380

1700

2080

2520

3020

3430

3920

4360

4770

5490

 

40

30

0

0

0

0

0

530

660

820

1010

1240

1520

1840

2200

2500

2850

3170

3470

3990

 

50

37

0

0

0

0

0

0

540

660

820

1000

1220

1480

1770

2010

2290

2550

2780

3190

 

60

45

0

0

0

0

0

0

0

560

690

850

1030

1250

1500

1700

1940

2150

2350

2700

 

75

55

0

0

0

0

0

0

0

0

570

700

860

1050

1270

1440

1660

1850

2030

2350

 

100

75

0

0

0

0

0

0

0

0

0

510

630

760

910

1030

1180

1310

1430

1650

 

125

90

0

0

0

0

0

0

0

0

0

0

0

620

740

840

950

1060

1160

1330

 

150

110

0

0

0

0

0

0

0

0

0

0

0

0

620

700

790

880

960

1090

 

175

130

0

0

0

0

0

0

0

0

0

0

0

0

0

650

750

840

920

1070

 

200

150

0

0

0

0

0

0

0

0

0

0

0

0

0

0

630

700

760

880

Lengths in BOLD only meet the US National Electrical Code ampacity requirements for individual conductors in free air or water. Lengths NOT in bold meet NEC ampacity requirements for either individual conductors or jacketed cable. See page 11 for additional details.

Continued on page 17

16

Image 19
Contents Submersible Motors Important Information for Installers of this Equipment Commitment to Quality Page Submersible Motors Application Installation Maintenance ManualMounting Position Application All MotorsStorage Frequency of StartsTorque Required Examples Transformer Capacity Single-Phase or Three-PhaseEffects of Torque Transformer CapacityKVA Use of Engine Driven Generators Single-Phase or Three-PhaseUse of Check Valves Engine Driven GeneratorsMotor Water Temperature and FlowFlow Inducer Sleeve Required Cooling FlowMinimum gpm l/m Required for 3 ft/s .91 m/sec Flow Rate Head Loss From Flow Past MotorHot Water Applications Standard Motors Head Loss in Feet Meters at Various Flow RatesHeat Factor Multiplier at 3 ft/s .91 m/sec Flow Rate Service Factor HorsepowerMaximum Water Temperature Hot Water Applications ExampleControl Box and Panel Environment Drawdown SealsGrounding Control Boxes and Panels Grounding Surge ArrestorsQD Relays Solid State Application Single-Phase MotorsWire Control Boxes Wire Motor Solid State Controls250 120180 200Actual Length Formula Two or More Different Cable Sizes Can Be UsedSingle-Phase Motor Specifications 60 Hz 3450 rpm Single-Phase Motor Fuse Sizing Buck-Boost Transformers Auxiliary Running CapacitorsBuck-Boost Transformer Sizing Application Three-Phase Motors Three-Phase 60 C Cable 450 140 220150 240 250 400280 150200 250 260Three-Phase 75 C Cable 340 400 490 120 180130 340 420Efficiency % Locked Rotor Amps Three-Phase Motor Specifications 60 HzFull Load Maximum Amps Watts575 Three-Phase Motor Fuse SizingEfficiency % KW Volts Amps Watts100 150 200 175 250 225 125 110 300 17.5 Efficiency Locked Rotor Amps Rating Full Load MaximumDual Element Furnas 60 Hz 4 MotorsHeaters for Overload Relays60 Hz 6 Motors Nema Heaters for AdjustableFootnotes for Tables 28, 29, Submersible Pump Installation Check List Date Filled In By Pump MotorIncoming Voltage Power SupplyTransformers Control PanelControls and Protective Devices InstallationVoltage To Motor Insulation CheckAmps To Motor 60 Hz 8 Motors Recommended Adjustable Overload RelaysMotor Kvar Required for PF SubMonitor Three-Phase ProtectionPower Factor Correction KVAR Required 60 HzLine Voltage Control Three-Phase Starter DiagramsChecking and Correcting Rotation and Current Unbalance Three-Phase Power UnbalancePhase Converters Three-Phase Motor Lead IdentificationInline Booster Pump Systems Reduced Voltage StartersFeed Water Temperature C AIR Franklin Cable chart See 12. WiringSource of Cable Ampacity Availability Variable Speed Submersible Pump Operation, Inverter Drives Dimensions Standard Water Well Installation All MotorsSubmersible Leads and Cables Tightening Motor Lead Connector Jam NutPump to Motor Coupling Shaft Height and Free End PlayMotor Starts Too Often Maintenance All MotorsSystem Troubleshooting Motor Does Not StartMotor Runs But Overload Protector Trips Motor Runs ContinuouslyResistance Preliminary Tests All Sizes Single- and Three-PhaseResistance of Drop Cable ohms Insulation Resistance ReadingsNormal ohm and Megohm Values Between All Leads and Ground Checking and Repairing Procedures Power On Single-Phase Control BoxesOhmmeter Tests QD, Solid State Control Box Power OffOverload Kits 60 Hz QD Relay Replacement Kits QD Capacitor Replacement KitsQD Control Box Parts 60 Hz Control BOX Model no Capacitors MFD Volts Integral Horsepower Control Box Parts 60 HzOverload Relay Integral hp Contactor Replacement Kits Integral hp Capacitor Replacement KitsIntegral hp Overload Replacement Kits Integral hp Voltage Relay Replacement Kits1 hp QD Relay Control Box Wiring DiagramsHp Standard Hp Deluxe 282 201 Hp X-LARGE Unit Appears Dead Maintenance Electronic ProductsPumptec-Plus Troubleshooting During Installation Pumptec-PlusPumptec-Plus Troubleshooting After Installation QD Pumptec and Pumptec QD Pumptec & Pumptec TroubleshootingSubDrive75, 150, 300, MonoDrive, & MonoDrive XT SubDrive/MonoDrive TroubleshootingSubMonitor SubMonitor TroubleshootingSubtrol-Plus Obsolete See SubMonitor Subtrol-Plus Troubleshooting After InstallationGreen Off Time Light on Igbt AbbreviationsPage Page Page Toll Free Help from a Friend