Franklin 2007 manual Reduced Voltage Starters, Inline Booster Pump Systems

Page 44

Application – Three-Phase Motors

Reduced Voltage Starters

All Franklin three-phase submersible motors are suitable for full-voltage starting. Under this condition the motor speed goes from zero to full speed within a half second or less. The motor current goes from zero to locked rotor amps, then drops to running amps at full speed. This may dim lights, cause momentary voltage dips

to other electrical equipment, and shock power distribution transformers.

In some cases the power companies may require reduced-voltage starters to limit this voltage dip. There are also times when reduced-voltage starters may be desirable to reduce motor starting torque thus reducing the stress on shafts, couplings, and discharge piping. Reduced-voltage starters also slow the rapid acceleration of the water on start-up to help control upthrust and water hammer.

Reduced-voltage starters may not be required if the maximum recommended cable length is used. With maximum recommended cable length there is a 5% voltage drop in the cable at running amps, resulting in about 20% reduction in starting current and about 36% reduction in starting torque compared to having rated voltage at the motor. This may be enough reduction in starting current so that reduced-voltage starters are not required.

Three-Lead Motors: Autotransformer or solid-state reduced-voltage starters may be used for soft-starting standard three-phase motors.

When autotransformer starters are used, the motor should be supplied with at least 55% of rated voltage to ensure adequate starting torque. Most autotransformer starters have 65% and 80% taps. Setting the taps on these starters depends on the percentage of the

maximum allowable cable length used in the system. If the cable length is less than 50% of the maximum allowable, either the 65% or the 80% taps may be used. When the cable length is more than 50% of allowable, the 80% tap should be used.

Six-Lead Motors: Wye-Delta starters are used with six-lead Wye-Delta motors. All Franklin 6" and 8" three-phase motors are available in six-lead Wye-Delta construction. Consult the factory for details and availability. Part winding starters are not compatible with Franklin Electric submersible motors and should not be used.

Wye-Delta starters of the open-transition type, which momentarily interrupt power during the starting cycle, are not recommended. Closed-transition starters have no interruption of power during the start cycle and can be used with satisfactory results.

Reduced-voltage starters have adjustable settings for acceleration ramp time, typically preset at 30 seconds. They must be adjusted so the motor is at full voltage within THREE SECONDS MAXIMUM to prevent excessive radial and thrust bearing wear.

If Subtrol-Plus or SubMonitor is used the acceleration time must be set to TWO SECONDS MAXIMUM due to the 3 second reaction time of the Subtrol-Plus or SubMonitor.

Solid-state starters AKA soft starts may not be compatible with Subtrol-Plus/SubMonitor. However, in some cases a bypass contactor has been used. Consult the factory for details.

During shutdown, Franklin Electric’s recommendation is for the power to be removed, allowing the pump/motor to coast down. Stopping the motor by ramping down the voltage is possible, but should be limited to three (3) seconds maximum.

Inline Booster Pump Systems

Franklin Electric offers three different types of motors for non-vertical applications.

1.The Booster motors are specifi cally designed for booster applications. They are the “Best Choice” for sealed Reverse Osmosis applications.

These motors are the result of two years of focused development and bring additional value and durability to booster module systems. These motors are

only available to OEMs or Distributors who have demonstrated capability in Booster Module systems design and operation and adhere to Franklin’s Application Manual requirements.

2.The Hi-Tempmotors have many of the internal design features of the Booster motor. It’s additional length allows for higher temperature handling and the Sand Fighter sealing system provides greater abrasion resistance. One or both of these conditions

are often experienced in open atmosphere applications such as lakes, ponds, etc.

3.The Standard Vertical Water Well (40-125 hp) motors can be adapted to non-vertical applications when applied per the below guidelines. However, they will be more sensitive to application variances than the other two designs.

All of the above motors must be applied per the guidelines listed below. In addition, for all applications where the motor is applied in a sealed system, a Submersible Motor Booster Installation Record (Form 3655) or its equivalent must be completed at startup and received by Franklin Electric within 60 days. A sealed system is one where the motor and pump intake are mounted in a sleeve and the water feeding the pump intake is not open to the atmosphere.

35

Image 44
Contents Submersible Motors Important Information for Installers of this Equipment Commitment to Quality Page Application Installation Maintenance Manual Submersible MotorsApplication All Motors StorageFrequency of Starts Mounting PositionTransformer Capacity Single-Phase or Three-Phase Effects of TorqueTransformer Capacity Torque Required ExamplesUse of Engine Driven Generators Single-Phase or Three-Phase Use of Check ValvesEngine Driven Generators KVAWater Temperature and Flow Flow Inducer SleeveRequired Cooling Flow MotorHead Loss From Flow Past Motor Hot Water Applications Standard MotorsHead Loss in Feet Meters at Various Flow Rates Minimum gpm l/m Required for 3 ft/s .91 m/sec Flow RateService Factor Horsepower Maximum Water TemperatureHot Water Applications Example Heat Factor Multiplier at 3 ft/s .91 m/sec Flow RateDrawdown Seals Grounding Control Boxes and PanelsGrounding Surge Arrestors Control Box and Panel EnvironmentApplication Single-Phase Motors Wire Control BoxesWire Motor Solid State Controls QD Relays Solid State120 180200 250Two or More Different Cable Sizes Can Be Used Actual Length FormulaSingle-Phase Motor Specifications 60 Hz 3450 rpm Single-Phase Motor Fuse Sizing Buck-Boost Transformer Sizing Auxiliary Running CapacitorsBuck-Boost Transformers Application Three-Phase Motors Three-Phase 60 C Cable 140 220 150 240250 400 450150 200 250260 280Three-Phase 75 C Cable 120 180 130340 420 340 400 490Three-Phase Motor Specifications 60 Hz Full Load MaximumAmps Watts Efficiency % Locked Rotor AmpsThree-Phase Motor Fuse Sizing 575KW Volts Amps Watts Efficiency %100 150 200 175 250 225 125 110 300 17.5 Rating Full Load Maximum Efficiency Locked Rotor AmpsDual Element 60 Hz 4 Motors Heaters forOverload Relays FurnasFootnotes for Tables 28, 29, Nema Heaters for Adjustable60 Hz 6 Motors Submersible Pump Installation Check List Date Filled In By Motor PumpPower Supply TransformersControl Panel Incoming VoltageInstallation Controls and Protective DevicesAmps To Motor Insulation CheckVoltage To Motor Recommended Adjustable Overload Relays 60 Hz 8 MotorsSubMonitor Three-Phase Protection Power Factor CorrectionKVAR Required 60 Hz Motor Kvar Required for PFThree-Phase Starter Diagrams Line Voltage ControlThree-Phase Power Unbalance Checking and Correcting Rotation and Current UnbalanceThree-Phase Motor Lead Identification Phase ConvertersReduced Voltage Starters Inline Booster Pump SystemsFeed Water Temperature C Source of Cable Ampacity Franklin Cable chart See 12. WiringAIR Availability Variable Speed Submersible Pump Operation, Inverter Drives Installation All Motors Dimensions Standard Water WellTightening Motor Lead Connector Jam Nut Pump to Motor CouplingShaft Height and Free End Play Submersible Leads and CablesMaintenance All Motors System TroubleshootingMotor Does Not Start Motor Starts Too OftenMotor Runs Continuously Motor Runs But Overload Protector TripsPreliminary Tests All Sizes Single- and Three-Phase ResistanceNormal ohm and Megohm Values Between All Leads and Ground Insulation Resistance ReadingsResistance of Drop Cable ohms Single-Phase Control Boxes Checking and Repairing Procedures Power OnQD, Solid State Control Box Power Off Ohmmeter TestsQD Control Box Parts 60 Hz QD Capacitor Replacement KitsOverload Kits 60 Hz QD Relay Replacement Kits Overload Relay Integral Horsepower Control Box Parts 60 HzControl BOX Model no Capacitors MFD Volts Integral hp Capacitor Replacement Kits Integral hp Overload Replacement KitsIntegral hp Voltage Relay Replacement Kits Integral hp Contactor Replacement KitsControl Box Wiring Diagrams 1 hp QD RelayHp Standard Hp Deluxe 282 201 Hp X-LARGE Maintenance Electronic Products Pumptec-Plus Troubleshooting During InstallationPumptec-Plus Unit Appears DeadPumptec-Plus Troubleshooting After Installation QD Pumptec & Pumptec Troubleshooting QD Pumptec and PumptecSubDrive/MonoDrive Troubleshooting SubDrive75, 150, 300, MonoDrive, & MonoDrive XTSubMonitor Troubleshooting SubMonitorGreen Off Time Subtrol-Plus Troubleshooting After InstallationSubtrol-Plus Obsolete See SubMonitor Light on Abbreviations IgbtPage Page Page Toll Free Help from a Friend