Franklin 2007 manual Transformer Capacity Single-Phase or Three-Phase, Effects of Torque

Page 7

Application – All Motors

Transformer Capacity - Single-Phase or Three-Phase

Distribution transformers must be adequately sized to satisfy the kVA requirements of the submersible motor. When transformers are too small to supply the load, there is a reduction in voltage to the motor.

Table 4 references the motor horsepower rating, single- phase and three-phase, total effective kVA required, and

the smallest transformer required for open or closed three-phase systems. Open systems require larger transformers since only two transformers are used.

Other loads would add directly to the kVA sizing requirements of the transformer bank.

Table 4 Transformer Capacity

MOTOR RATING

HP

KW

1.51.1

21.5

32.2

5

3.7

7.55.5

10

7.5

15

11

20

15

25

18.5

30

22

40

30

50

37

60

45

75

55

100

75

125

90

150

110

175130

200150

TOTAL

SMALLEST KVA RATING-EACH TRANSFORMER

EFFECTIVE

OPEN WYE

CLOSED

KVA

OR DELTA

WYE OR DELTA

REQUIRED

2- TRANSFORMERS

3- TRANSFORMERS

3

 

1

 

2

 

4

2

1.5

 

5

3

2

 

7.5

5

3

 

 

 

 

 

10

7.5

5

 

15

10

5

 

20

15

7.5

 

25

15

10

 

30

20

10

 

 

 

 

 

40

25

15

 

50

30

20

 

60

35

20

 

75

40

25

 

90

50

30

 

 

 

 

 

120

65

40

 

150

85

50

 

175

100

60

 

200

115

70

 

230

130

75

 

 

 

 

 

NOTE: Standard kVA ratings are shown. If power company experience and practice allows transformer loading higher than standard, higher loading values may be used to meet total effective kVA required, provided correct voltage and balance is maintained.

Effects of Torque

During starting of a submersible pump, the torque developed by the motor must be supported through the pump, delivery pipe or other supports. Most pumps rotate in the direction which causes unscrewing torque on right-handed threaded pipe or pump stages. All threaded joints, pumps and other parts of the pump support system must be capable of withstanding the maximum torque repeatedly without loosening or breaking. Unscrewing joints will break electrical cable and may cause loss of the pump-motor unit.

To safely withstand maximum unscrewing torques with a minimum safety factor of 1.5, tightening all theaded joints to at least 10 lb-ft per motor horsepower is recommended (table 4A). It may be necessary to tack or strap weld pipe joints on high horsepower pumps, especially at shallower settings.

Table 4A Torque Required (Examples)

MOTOR RATING

HP

KW

1 hp & Less

0.75 kW & Less

20 hp

15 kW

75 hp

55 kW

200 hp

150 kW

MINIMUM SAFE TORQUE-LOAD

10lb-ft 200 lb-ft 750 lb-ft

2000 lb-ft

4

Image 7
Contents Submersible Motors Important Information for Installers of this Equipment Commitment to Quality Page Submersible Motors Application Installation Maintenance ManualMounting Position Application All MotorsStorage Frequency of StartsTorque Required Examples Transformer Capacity Single-Phase or Three-PhaseEffects of Torque Transformer CapacityKVA Use of Engine Driven Generators Single-Phase or Three-PhaseUse of Check Valves Engine Driven GeneratorsMotor Water Temperature and FlowFlow Inducer Sleeve Required Cooling FlowMinimum gpm l/m Required for 3 ft/s .91 m/sec Flow Rate Head Loss From Flow Past MotorHot Water Applications Standard Motors Head Loss in Feet Meters at Various Flow RatesHeat Factor Multiplier at 3 ft/s .91 m/sec Flow Rate Service Factor HorsepowerMaximum Water Temperature Hot Water Applications ExampleControl Box and Panel Environment Drawdown SealsGrounding Control Boxes and Panels Grounding Surge ArrestorsQD Relays Solid State Application Single-Phase MotorsWire Control Boxes Wire Motor Solid State Controls250 120180 200Actual Length Formula Two or More Different Cable Sizes Can Be UsedSingle-Phase Motor Specifications 60 Hz 3450 rpm Single-Phase Motor Fuse Sizing Buck-Boost Transformers Auxiliary Running CapacitorsBuck-Boost Transformer Sizing Application Three-Phase Motors Three-Phase 60 C Cable 450 140 220150 240 250 400280 150200 250 260Three-Phase 75 C Cable 340 400 490 120 180130 340 420Efficiency % Locked Rotor Amps Three-Phase Motor Specifications 60 HzFull Load Maximum Amps Watts575 Three-Phase Motor Fuse SizingEfficiency % KW Volts Amps Watts100 150 200 175 250 225 125 110 300 17.5 Efficiency Locked Rotor Amps Rating Full Load MaximumDual Element Furnas 60 Hz 4 MotorsHeaters for Overload Relays60 Hz 6 Motors Nema Heaters for AdjustableFootnotes for Tables 28, 29, Submersible Pump Installation Check List Date Filled In By Pump MotorIncoming Voltage Power SupplyTransformers Control PanelControls and Protective Devices InstallationVoltage To Motor Insulation CheckAmps To Motor 60 Hz 8 Motors Recommended Adjustable Overload RelaysMotor Kvar Required for PF SubMonitor Three-Phase ProtectionPower Factor Correction KVAR Required 60 HzLine Voltage Control Three-Phase Starter DiagramsChecking and Correcting Rotation and Current Unbalance Three-Phase Power UnbalancePhase Converters Three-Phase Motor Lead IdentificationInline Booster Pump Systems Reduced Voltage StartersFeed Water Temperature C AIR Franklin Cable chart See 12. WiringSource of Cable Ampacity Availability Variable Speed Submersible Pump Operation, Inverter Drives Dimensions Standard Water Well Installation All MotorsSubmersible Leads and Cables Tightening Motor Lead Connector Jam NutPump to Motor Coupling Shaft Height and Free End PlayMotor Starts Too Often Maintenance All MotorsSystem Troubleshooting Motor Does Not StartMotor Runs But Overload Protector Trips Motor Runs ContinuouslyResistance Preliminary Tests All Sizes Single- and Three-PhaseResistance of Drop Cable ohms Insulation Resistance ReadingsNormal ohm and Megohm Values Between All Leads and Ground Checking and Repairing Procedures Power On Single-Phase Control BoxesOhmmeter Tests QD, Solid State Control Box Power OffOverload Kits 60 Hz QD Relay Replacement Kits QD Capacitor Replacement KitsQD Control Box Parts 60 Hz Control BOX Model no Capacitors MFD Volts Integral Horsepower Control Box Parts 60 HzOverload Relay Integral hp Contactor Replacement Kits Integral hp Capacitor Replacement KitsIntegral hp Overload Replacement Kits Integral hp Voltage Relay Replacement Kits1 hp QD Relay Control Box Wiring DiagramsHp Standard Hp Deluxe 282 201 Hp X-LARGE Unit Appears Dead Maintenance Electronic ProductsPumptec-Plus Troubleshooting During Installation Pumptec-PlusPumptec-Plus Troubleshooting After Installation QD Pumptec and Pumptec QD Pumptec & Pumptec TroubleshootingSubDrive75, 150, 300, MonoDrive, & MonoDrive XT SubDrive/MonoDrive TroubleshootingSubMonitor SubMonitor TroubleshootingSubtrol-Plus Obsolete See SubMonitor Subtrol-Plus Troubleshooting After InstallationGreen Off Time Light on Igbt AbbreviationsPage Page Page Toll Free Help from a Friend