Franklin 2007 Use of Engine Driven Generators Single-Phase or Three-Phase, Use of Check Valves

Page 8

Application – All Motors

Use of Engine Driven Generators - Single-Phase or Three-Phase

Table 5 lists minimum generator sizes based on typical 80 °C rise continuous duty generators, with 35% maximum voltage dip during starting, for Franklin’s three- wire motors, single- or three-phase.

This is a general chart. The generator manufacturer should be consulted whenever possible, especially on larger sizes.

There are two types of generators available: externally and internally regulated. Most are externally regulated. They use an external voltage regulator that senses the output voltage. As the voltage dips at motor start-up, the regulator increases the output voltage of the generator.

Internally regulated (self-excited) generators have an extra winding in the generator stator. The extra winding senses the output current to automatically adjust the output voltage.

Generators must be sized to deliver at least 65% of the rated voltage during starting to ensure adequate starting torque. Besides sizing, generator frequency is important as the motor speed varies with the frequency (Hz). Due to pump affi nity laws, a pump running at 1 to 2 Hz below motor nameplate frequency design will not meet its performance curve. Conversely, a pump running at 1 to 2 Hz above may trip overloads.

Generator Operation

Always start the generator before the motor is started and always stop the motor before the generator is shut down. The motor thrust bearing may be damaged if the generator is allowed to coast down with the motor running. This same condition occurs when the generator is allowed to run out of fuel.

Follow generator manufacturer’s recommendations for de-rating at higher elevations or using natural gas.

Table 5 Engine Driven Generators

NOTE: This chart applies to 3-wire or 3-phase motors. For best starting of 2-wire motors, the minimum generator rating is 50% higher than shown.

MOTOR RATING

 

MINIMUM RATING OF GENERATOR

 

HP

KW

EXTERNALLY REGULATED

INTERNALLY REGULATED

KW

KVA

KW

KVA

 

 

1/3

0.25

1.5

1.9

1.2

 

1.5

1/2

0.37

2

2.5

1.5

 

1.9

3/4

0.55

3

3.8

2

 

2.5

1

0.75

4

5.0

2.5

 

3.13

1.5

1.1

5

6.25

3

 

3.8

2

1.5

7.5

9.4

4

 

5

3

2.2

10

12.5

5

 

6.25

5

3.7

15

18.75

7.5

 

9.4

7.5

5.5

20

25.0

10

 

12.5

10

7.5

30

37.5

15

 

18.75

15

11

40

50

20

 

25

20

15

60

75

25

 

31

25

18.5

75

94

30

 

37.50

30

22

100

125

40

 

50

40

30

100

125

50

 

62.5

50

37

150

188

60

 

75

60

45

175

220

75

 

94

75

55

250

313

100

 

125

100

75

300

375

150

 

188

125

90

375

469

175

 

219

150

110

450

563

200

 

250

175

130

525

656

250

 

313

200

150

600

750

275

 

344

WARNING: To prevent accidental electrocution, automatic or manual transfer switches must be used any time a generator is used as standby or back up on power lines. Contact power company for use and approval.

Use of Check Valves

It is recommended that one or more check valves always be used in submersible pump installations. If the pump does not have a built-in check valve, a line check valve should be installed in the discharge line within 25 feet of the pump and below the draw down level of the water supply. For deeper settings, check valves should be installed per the manufacturer’s recommendations. More than one check valve may be required, but more than the recommended number of check valves should not

be used.

Swing type check valves are not acceptable and should never be used with submersible motors/pumps. Swing type check valves have a slower reaction time which can cause water hammer (see next page). Internal pump check valves or spring loaded check valves close quickly and help eliminate water hammer.

Check valves are used to hold pressure in the system when the pump stops. They also prevent backspin, water

hammer and upthrust. Any of these can lead to early pump or motor failure.

NOTE: Only positive sealing check valves should be used in submersible installations. Although drilling the check valves or using drain-back check valves may prevent back spinning, they create upthrust and water hammer problems.

A.Backspin - With no check valve or a failed check valve, the water in the drop pipe and the water in the system can fl ow down the discharge pipe when the motor stops. This can cause the pump to rotate in a reverse direction. If the motor is started while it is backspinning, an excessive force is placed across the pump-motor assembly that can cause impeller damage, motor or pump shaft breakage, excessive bearing wear, etc.

B.Upthrust - With no check valve, a leaking check valve, or drilled check valve, the unit starts under

5

Image 8
Contents Submersible Motors Important Information for Installers of this Equipment Commitment to Quality Page Application Installation Maintenance Manual Submersible MotorsApplication All Motors StorageFrequency of Starts Mounting PositionTransformer Capacity Single-Phase or Three-Phase Effects of TorqueTransformer Capacity Torque Required ExamplesUse of Engine Driven Generators Single-Phase or Three-Phase Use of Check ValvesEngine Driven Generators KVAWater Temperature and Flow Flow Inducer SleeveRequired Cooling Flow MotorHead Loss From Flow Past Motor Hot Water Applications Standard MotorsHead Loss in Feet Meters at Various Flow Rates Minimum gpm l/m Required for 3 ft/s .91 m/sec Flow RateService Factor Horsepower Maximum Water TemperatureHot Water Applications Example Heat Factor Multiplier at 3 ft/s .91 m/sec Flow RateDrawdown Seals Grounding Control Boxes and PanelsGrounding Surge Arrestors Control Box and Panel EnvironmentApplication Single-Phase Motors Wire Control BoxesWire Motor Solid State Controls QD Relays Solid State120 180200 250Two or More Different Cable Sizes Can Be Used Actual Length FormulaSingle-Phase Motor Specifications 60 Hz 3450 rpm Single-Phase Motor Fuse Sizing Buck-Boost Transformer Sizing Auxiliary Running CapacitorsBuck-Boost Transformers Application Three-Phase Motors Three-Phase 60 C Cable 140 220 150 240250 400 450150 200 250260 280Three-Phase 75 C Cable 120 180 130340 420 340 400 490Three-Phase Motor Specifications 60 Hz Full Load MaximumAmps Watts Efficiency % Locked Rotor AmpsThree-Phase Motor Fuse Sizing 575KW Volts Amps Watts Efficiency %100 150 200 175 250 225 125 110 300 17.5 Rating Full Load Maximum Efficiency Locked Rotor AmpsDual Element 60 Hz 4 Motors Heaters forOverload Relays FurnasFootnotes for Tables 28, 29, Nema Heaters for Adjustable60 Hz 6 Motors Submersible Pump Installation Check List Date Filled In By Motor PumpPower Supply TransformersControl Panel Incoming VoltageInstallation Controls and Protective DevicesAmps To Motor Insulation CheckVoltage To Motor Recommended Adjustable Overload Relays 60 Hz 8 MotorsSubMonitor Three-Phase Protection Power Factor CorrectionKVAR Required 60 Hz Motor Kvar Required for PFThree-Phase Starter Diagrams Line Voltage ControlThree-Phase Power Unbalance Checking and Correcting Rotation and Current UnbalanceThree-Phase Motor Lead Identification Phase ConvertersReduced Voltage Starters Inline Booster Pump SystemsFeed Water Temperature C Source of Cable Ampacity Franklin Cable chart See 12. WiringAIR Availability Variable Speed Submersible Pump Operation, Inverter Drives Installation All Motors Dimensions Standard Water WellTightening Motor Lead Connector Jam Nut Pump to Motor CouplingShaft Height and Free End Play Submersible Leads and CablesMaintenance All Motors System TroubleshootingMotor Does Not Start Motor Starts Too OftenMotor Runs Continuously Motor Runs But Overload Protector TripsPreliminary Tests All Sizes Single- and Three-Phase ResistanceNormal ohm and Megohm Values Between All Leads and Ground Insulation Resistance ReadingsResistance of Drop Cable ohms Single-Phase Control Boxes Checking and Repairing Procedures Power OnQD, Solid State Control Box Power Off Ohmmeter TestsQD Control Box Parts 60 Hz QD Capacitor Replacement KitsOverload Kits 60 Hz QD Relay Replacement Kits Overload Relay Integral Horsepower Control Box Parts 60 HzControl BOX Model no Capacitors MFD Volts Integral hp Capacitor Replacement Kits Integral hp Overload Replacement KitsIntegral hp Voltage Relay Replacement Kits Integral hp Contactor Replacement KitsControl Box Wiring Diagrams 1 hp QD RelayHp Standard Hp Deluxe 282 201 Hp X-LARGE Maintenance Electronic Products Pumptec-Plus Troubleshooting During InstallationPumptec-Plus Unit Appears DeadPumptec-Plus Troubleshooting After Installation QD Pumptec & Pumptec Troubleshooting QD Pumptec and PumptecSubDrive/MonoDrive Troubleshooting SubDrive75, 150, 300, MonoDrive, & MonoDrive XTSubMonitor Troubleshooting SubMonitorGreen Off Time Subtrol-Plus Troubleshooting After InstallationSubtrol-Plus Obsolete See SubMonitor Light on Abbreviations IgbtPage Page Page Toll Free Help from a Friend