Franklin 2007 manual Feed Water Temperature C

Page 45

Application – Three-Phase Motors

Inline Booster Pump Systems (continued)

Design And Operational Requirements

1.Non-Vertical Operation: Vertical Shaft-up (0°) to Horizontal (90°) operation is acceptable as long as the pump transmits “down-thrust” to the motor within 3 seconds after start-up and continuously during operation. However, it is best practice to provide a positive slope whenever it is possible, even if it is only a few degrees.

2.Motor, Sleeve, and Pump Support System: The booster sleeve ID must be sized according to the motor cooling and pump NPSHR requirements. The support system must support the motor’s weight, prevent motor rotation and keep the motor and pump aligned. The support system must also allow for thermal axial expansion of the motor without creating binding forces.

3.Motor Support Points: A minimum of two support points are required on the motor. One in the motor/ pump fl ange connection area and one in the bottom end of the motor area. The motor castings, not the shell area, are recommended as support points. If the support is a full length support and/or has bands in the shell area, they must not restrict heat transfer or deform the shell.

4.Motor Support Material and Design: The support system shall not create any areas of cavitation or other areas of reduced fl ow less than the minimum rate required by this manual. They should also be designed to minimize turbulence and vibration and provide stable alignment. The support materials and locations must not inhibit the heat transfer away from the motor.

5.Motor and Pump Alignment: The maximum allowable misalignment between the motor, pump, and pump discharge is 0.025 inch per 12 inches of length (2 mm per 1000 mm of length). This must be measured in both directions along the assembly using the motor/pump fl ange connection as the starting point. The booster sleeve and support system must be rigid enough to maintain this alignment during assembly, shipping, operation and maintenance.

6.The best motor lubrication and heat resistance is obtained with the factory based propylene glycol

fi ll solution. Only when an application MUST HAVE deionized (DI) water should the factory fi ll solution be replaced. When a deionized water fi ll is required, the motor must be derated as indicated on the below chart. The exchange of the motor fi ll solution to DI

water must be done by an approved Franklin service shop or representative using a vacuum fill system per Franklin’s Motor Service Manual instruction. The motor shell then must be permanently stamped with a D closely behind the Serial Number.

The maximum pressure that can be applied to the motor internal components during the removal of the factory fi ll solution is 7 psi (0.5 bar.)

Derating Factor for Motors That Must Have Their Factory Fill Replaced With Deionized Water 8" Encapsulated Motor

 

1.8

 

 

 

 

 

 

 

 

 

 

 

 

 

1.75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Multiplier

1.65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.55

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Load

1.45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pump

1.35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.00 Service

Factor

 

(50Hz)

 

 

 

 

1.25

 

 

 

 

 

 

 

 

 

1.3

 

 

 

 

 

 

 

 

 

 

 

 

 

1.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.15 Service Factor

 

(60Hz)

 

 

 

 

 

 

 

 

1.05

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

35

30

25

20

15

10

Feed Water Temperature (°C)

FIG. 12

First: Determine maximum Feed Water Temperature that will be experienced in this application. If the feed water exceeds the maximum ambient of the motor, both the DI water derating and a hot water application derating must be applied.

Second: Determine the Pump Load Multiplier from the appropriate Service Factor curve. (Typical 1.15 Service Factor is for 60 Hz ratings &1.00 Service Factor for 50 Hz ratings).

Third: Multiply the Pump Load Requirement times the pump load multiplier number indicated on the vertical axis to determine the Minimum Motor Nameplate Rating.

Fourth: Select a motor with a nameplate equal or higher than the above calculated value.

7.Motor Alterations - Sand Slinger & Check Valve Plug: On 6" and 8" motors, the rubber sand slinger located on the shaft must be removed. The pipe plug covering the check valve must be removed from Ni- resist and 316 SS motors. The special Booster motor already has these alterations made.

8.Frequency of Starts: Fewer than 10 starts per

24-hour period are recommended. Allow at least 20

minutes between shutdown and start-up of the motor.

36

Image 45
Contents Submersible Motors Important Information for Installers of this Equipment Commitment to Quality Page Submersible Motors Application Installation Maintenance ManualStorage Application All MotorsFrequency of Starts Mounting PositionEffects of Torque Transformer Capacity Single-Phase or Three-PhaseTransformer Capacity Torque Required ExamplesUse of Check Valves Use of Engine Driven Generators Single-Phase or Three-PhaseEngine Driven Generators KVAFlow Inducer Sleeve Water Temperature and FlowRequired Cooling Flow MotorHot Water Applications Standard Motors Head Loss From Flow Past MotorHead Loss in Feet Meters at Various Flow Rates Minimum gpm l/m Required for 3 ft/s .91 m/sec Flow RateMaximum Water Temperature Service Factor HorsepowerHot Water Applications Example Heat Factor Multiplier at 3 ft/s .91 m/sec Flow RateGrounding Control Boxes and Panels Drawdown SealsGrounding Surge Arrestors Control Box and Panel EnvironmentWire Control Boxes Application Single-Phase MotorsWire Motor Solid State Controls QD Relays Solid State180 120200 250Actual Length Formula Two or More Different Cable Sizes Can Be UsedSingle-Phase Motor Specifications 60 Hz 3450 rpm Single-Phase Motor Fuse Sizing Auxiliary Running Capacitors Buck-Boost TransformersBuck-Boost Transformer Sizing Application Three-Phase Motors Three-Phase 60 C Cable 150 240 140 220250 400 450200 250 150260 280Three-Phase 75 C Cable 130 120 180340 420 340 400 490Full Load Maximum Three-Phase Motor Specifications 60 HzAmps Watts Efficiency % Locked Rotor Amps575 Three-Phase Motor Fuse SizingEfficiency % KW Volts Amps Watts100 150 200 175 250 225 125 110 300 17.5 Efficiency Locked Rotor Amps Rating Full Load MaximumDual Element Heaters for 60 Hz 4 MotorsOverload Relays FurnasNema Heaters for Adjustable 60 Hz 6 MotorsFootnotes for Tables 28, 29, Submersible Pump Installation Check List Date Filled In By Pump MotorTransformers Power SupplyControl Panel Incoming VoltageControls and Protective Devices InstallationInsulation Check Voltage To MotorAmps To Motor 60 Hz 8 Motors Recommended Adjustable Overload RelaysPower Factor Correction SubMonitor Three-Phase ProtectionKVAR Required 60 Hz Motor Kvar Required for PFLine Voltage Control Three-Phase Starter DiagramsChecking and Correcting Rotation and Current Unbalance Three-Phase Power UnbalancePhase Converters Three-Phase Motor Lead IdentificationInline Booster Pump Systems Reduced Voltage StartersFeed Water Temperature C Franklin Cable chart See 12. Wiring AIRSource of Cable Ampacity Availability Variable Speed Submersible Pump Operation, Inverter Drives Dimensions Standard Water Well Installation All MotorsPump to Motor Coupling Tightening Motor Lead Connector Jam NutShaft Height and Free End Play Submersible Leads and CablesSystem Troubleshooting Maintenance All MotorsMotor Does Not Start Motor Starts Too OftenMotor Runs But Overload Protector Trips Motor Runs ContinuouslyResistance Preliminary Tests All Sizes Single- and Three-PhaseInsulation Resistance Readings Resistance of Drop Cable ohmsNormal ohm and Megohm Values Between All Leads and Ground Checking and Repairing Procedures Power On Single-Phase Control BoxesOhmmeter Tests QD, Solid State Control Box Power OffQD Capacitor Replacement Kits Overload Kits 60 Hz QD Relay Replacement KitsQD Control Box Parts 60 Hz Integral Horsepower Control Box Parts 60 Hz Control BOX Model no Capacitors MFD VoltsOverload Relay Integral hp Overload Replacement Kits Integral hp Capacitor Replacement KitsIntegral hp Voltage Relay Replacement Kits Integral hp Contactor Replacement Kits1 hp QD Relay Control Box Wiring DiagramsHp Standard Hp Deluxe 282 201 Hp X-LARGE Pumptec-Plus Troubleshooting During Installation Maintenance Electronic ProductsPumptec-Plus Unit Appears DeadPumptec-Plus Troubleshooting After Installation QD Pumptec and Pumptec QD Pumptec & Pumptec TroubleshootingSubDrive75, 150, 300, MonoDrive, & MonoDrive XT SubDrive/MonoDrive TroubleshootingSubMonitor SubMonitor TroubleshootingSubtrol-Plus Troubleshooting After Installation Subtrol-Plus Obsolete See SubMonitorGreen Off Time Light on Igbt AbbreviationsPage Page Page Toll Free Help from a Friend