Maintenance – All Motors

Insulation Resistance Readings

Table 45 Normal ohm and Megohm Values Between All Leads and Ground

CONDITION OF MOTOR AND LEADS

A new motor (without drop cable).

A used motor which can be reinstalled in well.

MOTOR IN WELL. READINGS ARE FOR DROP CABLE PLUS MOTOR.

New motor.

Motor in good condition.

Insulation damage, locate and repair.

 

OHMS VALUE

 

MEGOHM VALUE

 

200,000,000 (or more)

 

200.0 (or more)

 

 

 

 

 

10,000,000 (or more)

 

10.0 (or more)

 

 

 

 

 

 

 

2,000,000 (or more)

 

2.0 (or more)

 

 

500,000 - 2,000,000

 

0.50 - 2.0

 

 

Less than 500,000

 

Less than .50

 

 

 

 

 

 

Insulation resistance varies very little with rating. Motors of all hp, voltage, and phase rating have similar values of insulation resistance.

The table above is based on readings taken with a megohm meter with a 500 VDC output. Readings may vary using a lower voltage Ohmmeter, consult Franklin Electric if readings are in question.

Resistance of Drop Cable (ohms)

The values below are for copper conductors. If aluminum conductor drop cable is used, the resistance will be higher. To determine the actual resistance of the aluminum drop cable, divide the ohm readings from this chart by 0.61. This chart shows total resistance of cable from control to motor and back.

Winding Resistance Measuring

The winding resistance measured at the motor should fall within the values in tables 13, 22, 24 & 26. When measured through the drop cable, the resistance of the drop cable must be subtracted from the Ohmmeter readings to get the winding resistance of the motor. See table below.

Table 45A DC Resistance in ohms per 100 ft of Wire (Two conductors) @ 50 °F

AWG OR MCM WIRE SIZE (COPPER)

14

12

10

8

6

4

3

2

OHMS

0.544

0.338

0.214

0.135

0.082

0.052

0.041

0.032

1

1/0

2/0

3/0

4/0

250

300

350

400

500

600

700

0.026

0.021

0.017

0.013

0.010

0.0088

0.0073

0.0063

0.0056

0.0044

0.0037

0.0032

45

Image 54
Contents Submersible Motors Important Information for Installers of this Equipment Commitment to Quality Page Application Installation Maintenance Manual Submersible MotorsFrequency of Starts Application All MotorsStorage Mounting PositionTransformer Capacity Transformer Capacity Single-Phase or Three-PhaseEffects of Torque Torque Required ExamplesEngine Driven Generators Use of Engine Driven Generators Single-Phase or Three-PhaseUse of Check Valves KVARequired Cooling Flow Water Temperature and FlowFlow Inducer Sleeve MotorHead Loss in Feet Meters at Various Flow Rates Head Loss From Flow Past MotorHot Water Applications Standard Motors Minimum gpm l/m Required for 3 ft/s .91 m/sec Flow RateHot Water Applications Example Service Factor HorsepowerMaximum Water Temperature Heat Factor Multiplier at 3 ft/s .91 m/sec Flow RateGrounding Surge Arrestors Drawdown SealsGrounding Control Boxes and Panels Control Box and Panel EnvironmentWire Motor Solid State Controls Application Single-Phase MotorsWire Control Boxes QD Relays Solid State200 120180 250Two or More Different Cable Sizes Can Be Used Actual Length FormulaSingle-Phase Motor Specifications 60 Hz 3450 rpm Single-Phase Motor Fuse Sizing Auxiliary Running Capacitors Buck-Boost TransformersBuck-Boost Transformer Sizing Application Three-Phase Motors Three-Phase 60 C Cable 250 400 140 220150 240 450260 150200 250 280Three-Phase 75 C Cable 340 420 120 180130 340 400 490Amps Watts Three-Phase Motor Specifications 60 HzFull Load Maximum Efficiency % Locked Rotor AmpsThree-Phase Motor Fuse Sizing 575KW Volts Amps Watts Efficiency %100 150 200 175 250 225 125 110 300 17.5 Rating Full Load Maximum Efficiency Locked Rotor AmpsDual Element Overload Relays 60 Hz 4 MotorsHeaters for FurnasNema Heaters for Adjustable 60 Hz 6 MotorsFootnotes for Tables 28, 29, Submersible Pump Installation Check List Date Filled In By Motor PumpControl Panel Power SupplyTransformers Incoming VoltageInstallation Controls and Protective DevicesInsulation Check Voltage To MotorAmps To Motor Recommended Adjustable Overload Relays 60 Hz 8 MotorsKVAR Required 60 Hz SubMonitor Three-Phase ProtectionPower Factor Correction Motor Kvar Required for PFThree-Phase Starter Diagrams Line Voltage ControlThree-Phase Power Unbalance Checking and Correcting Rotation and Current UnbalanceThree-Phase Motor Lead Identification Phase ConvertersReduced Voltage Starters Inline Booster Pump SystemsFeed Water Temperature C Franklin Cable chart See 12. Wiring AIRSource of Cable Ampacity Availability Variable Speed Submersible Pump Operation, Inverter Drives Installation All Motors Dimensions Standard Water WellShaft Height and Free End Play Tightening Motor Lead Connector Jam NutPump to Motor Coupling Submersible Leads and CablesMotor Does Not Start Maintenance All MotorsSystem Troubleshooting Motor Starts Too OftenMotor Runs Continuously Motor Runs But Overload Protector TripsPreliminary Tests All Sizes Single- and Three-Phase ResistanceInsulation Resistance Readings Resistance of Drop Cable ohmsNormal ohm and Megohm Values Between All Leads and Ground Single-Phase Control Boxes Checking and Repairing Procedures Power OnQD, Solid State Control Box Power Off Ohmmeter TestsQD Capacitor Replacement Kits Overload Kits 60 Hz QD Relay Replacement KitsQD Control Box Parts 60 Hz Integral Horsepower Control Box Parts 60 Hz Control BOX Model no Capacitors MFD VoltsOverload Relay Integral hp Voltage Relay Replacement Kits Integral hp Capacitor Replacement KitsIntegral hp Overload Replacement Kits Integral hp Contactor Replacement KitsControl Box Wiring Diagrams 1 hp QD RelayHp Standard Hp Deluxe 282 201 Hp X-LARGE Pumptec-Plus Maintenance Electronic ProductsPumptec-Plus Troubleshooting During Installation Unit Appears DeadPumptec-Plus Troubleshooting After Installation QD Pumptec & Pumptec Troubleshooting QD Pumptec and PumptecSubDrive/MonoDrive Troubleshooting SubDrive75, 150, 300, MonoDrive, & MonoDrive XTSubMonitor Troubleshooting SubMonitorSubtrol-Plus Troubleshooting After Installation Subtrol-Plus Obsolete See SubMonitorGreen Off Time Light on Abbreviations IgbtPage Page Page Toll Free Help from a Friend