Page 41

Application – Three-Phase Motors

Three-Phase Starter Diagrams

Three-phase combination magnetic starters have two distinct circuits: a power circuit and a control circuit.

The power circuit consists of a circuit breaker or fused line switch, contacts, and overload heaters connecting incoming power lines L1, L2, L3 and the three-phase motor.

The control circuit consists of the magnetic coil, overload contacts and a control device such as a pressure switch. When the control device contacts are closed, current

ows through the magnetic contactor coil, the contacts close, and power is applied to the motor. Hand-Off-Auto switches, start timers, level controls and other control devices may also be in series in the control circuit.

L1 L2 L3

Line Voltage Control

This is the most common type of control encountered. Since the coil is connected directly across the power lines L1 and L2, the coil must match the line voltage.

FUSES

CONTACTS

PRESSURE SWITCH OR

OTHER CONTROL DEVICE

O.L. CONTACTS

COIL

OVERLOAD

HEATERS AND/OR

SUBTROL PLUS

Low Voltage Transformer Control

MOTOR

FIG. 7

L1 L2 L3

This control is used when it is desirable to operate push buttons or other control devices at some voltage lower than the motor voltage. The transformer primary must match the line voltage and the coil voltage must match the secondary voltage of the transformer.

FUSES

CONTACTS

TRANSFORMER

OVERLOAD HEATERS AND/OR SUBTROL PLUS

FUSE

PRESSURE SWITCH OR OTHER CONTROL DEVICE

O.L. CONTACTS

COIL

MOTOR

FIG. 8

 

L1 L2 L3

External Voltage Controls

Control of a power circuit by a lower circuit voltage can also be obtained by connecting to a separate control voltage source. The coil rating must match the control voltage source, such as 115 or 24 volts.

FUSES

CONTACTS

PRESSURE SWITCH OR

OTHER CONTROL DEVICE

 

O.L. CONTACTS

COIL

TO SEPARATE

 

CONTROL VOLTAGE

 

SOURCE

OVERLOAD

HEATER AND/OR

SUBTROL DEVICE

MOTOR

FIG. 9

32

Image 41
Contents Submersible Motors Important Information for Installers of this Equipment Commitment to Quality Page Submersible Motors Application Installation Maintenance ManualStorage Application All MotorsFrequency of Starts Mounting PositionEffects of Torque Transformer Capacity Single-Phase or Three-PhaseTransformer Capacity Torque Required ExamplesUse of Check Valves Use of Engine Driven Generators Single-Phase or Three-PhaseEngine Driven Generators KVAFlow Inducer Sleeve Water Temperature and FlowRequired Cooling Flow MotorHot Water Applications Standard Motors Head Loss From Flow Past MotorHead Loss in Feet Meters at Various Flow Rates Minimum gpm l/m Required for 3 ft/s .91 m/sec Flow RateMaximum Water Temperature Service Factor HorsepowerHot Water Applications Example Heat Factor Multiplier at 3 ft/s .91 m/sec Flow RateGrounding Control Boxes and Panels Drawdown SealsGrounding Surge Arrestors Control Box and Panel EnvironmentWire Control Boxes Application Single-Phase MotorsWire Motor Solid State Controls QD Relays Solid State180 120200 250Actual Length Formula Two or More Different Cable Sizes Can Be UsedSingle-Phase Motor Specifications 60 Hz 3450 rpm Single-Phase Motor Fuse Sizing Buck-Boost Transformer Sizing Auxiliary Running CapacitorsBuck-Boost Transformers Application Three-Phase Motors Three-Phase 60 C Cable 150 240 140 220250 400 450200 250 150260 280Three-Phase 75 C Cable 130 120 180340 420 340 400 490Full Load Maximum Three-Phase Motor Specifications 60 HzAmps Watts Efficiency % Locked Rotor Amps575 Three-Phase Motor Fuse SizingEfficiency % KW Volts Amps Watts100 150 200 175 250 225 125 110 300 17.5 Efficiency Locked Rotor Amps Rating Full Load MaximumDual Element Heaters for 60 Hz 4 MotorsOverload Relays FurnasFootnotes for Tables 28, 29, Nema Heaters for Adjustable60 Hz 6 Motors Submersible Pump Installation Check List Date Filled In By Pump MotorTransformers Power SupplyControl Panel Incoming VoltageControls and Protective Devices InstallationAmps To Motor Insulation CheckVoltage To Motor 60 Hz 8 Motors Recommended Adjustable Overload RelaysPower Factor Correction SubMonitor Three-Phase ProtectionKVAR Required 60 Hz Motor Kvar Required for PFLine Voltage Control Three-Phase Starter DiagramsChecking and Correcting Rotation and Current Unbalance Three-Phase Power UnbalancePhase Converters Three-Phase Motor Lead IdentificationInline Booster Pump Systems Reduced Voltage StartersFeed Water Temperature C Source of Cable Ampacity Franklin Cable chart See 12. WiringAIR Availability Variable Speed Submersible Pump Operation, Inverter Drives Dimensions Standard Water Well Installation All MotorsPump to Motor Coupling Tightening Motor Lead Connector Jam NutShaft Height and Free End Play Submersible Leads and CablesSystem Troubleshooting Maintenance All MotorsMotor Does Not Start Motor Starts Too OftenMotor Runs But Overload Protector Trips Motor Runs ContinuouslyResistance Preliminary Tests All Sizes Single- and Three-PhaseNormal ohm and Megohm Values Between All Leads and Ground Insulation Resistance ReadingsResistance of Drop Cable ohms Checking and Repairing Procedures Power On Single-Phase Control BoxesOhmmeter Tests QD, Solid State Control Box Power OffQD Control Box Parts 60 Hz QD Capacitor Replacement KitsOverload Kits 60 Hz QD Relay Replacement Kits Overload Relay Integral Horsepower Control Box Parts 60 HzControl BOX Model no Capacitors MFD Volts Integral hp Overload Replacement Kits Integral hp Capacitor Replacement KitsIntegral hp Voltage Relay Replacement Kits Integral hp Contactor Replacement Kits1 hp QD Relay Control Box Wiring DiagramsHp Standard Hp Deluxe 282 201 Hp X-LARGE Pumptec-Plus Troubleshooting During Installation Maintenance Electronic ProductsPumptec-Plus Unit Appears DeadPumptec-Plus Troubleshooting After Installation QD Pumptec and Pumptec QD Pumptec & Pumptec TroubleshootingSubDrive75, 150, 300, MonoDrive, & MonoDrive XT SubDrive/MonoDrive TroubleshootingSubMonitor SubMonitor TroubleshootingGreen Off Time Subtrol-Plus Troubleshooting After InstallationSubtrol-Plus Obsolete See SubMonitor Light on Igbt AbbreviationsPage Page Page Toll Free Help from a Friend