8.6.5 Set-up of group (Step 4)
It is possible to confirm and change the group information of the indoor unit and ventilation unit within each
Select the
Group No.:
Displays the group No.
Group information:
Displays the group configuration of the indoor unit or ventila- tion unit.
Unconnected indoor unit:
Displays the indoor unit, LOSSNAY (IC, KIC, AIC, LC) not set for the group.
Unconnected remote controller:
Displays the SC, GR, SR, AN, and RC which can be set for the group.
Confirm the group information. [Procedure]
1)Click the “/ ” button to select
Select the
2)Select the [OK] button after confirming the group information.
If it is not necessary to change or correct the information of each
*When the [Cancel] button is clicked, this setting is terminated to return to the initial window.
Change the group information. [Procedure]
1)Click the “/ ” button to select
Select the
2)Delete/add the unit icon.
Unit icon deletion:Click the unit icon to be deleted.
Unit icon addition:Click the unit icon to be added, from the Unconnected indoor unit and Unconnected remote controller columns to set it to the selected state. (The symbol of the selected unit is displayed by the pointer.)
When the group column to be added is clicked, the unit icon is displayed.
3)Select the [OK] button.
After fully completing the group information changes, click the [OK] button.
Note:
•When the group setting change screen is changed, it is possible to reflect the changed contents on the
•It cannot set the indoor unit
•Since the number of groups and the number of indoor units connectable to the GR, SR, and AN is limited, set the group corresponding with such limitations.
This group setting screen displays the number of groups and number of indoor units which allow the GR, SR, AN, and SC to be newly organized.
Table: Number of management groups and number of indoor units
Symbol | Equipment name | Number of management groups | |||
and number of indoor units | |||||
|
| ||||
|
|
| |||
|
|
| |||
GR | Group remote controller | 8 groups, 16 indoor units | |||
|
|
|
|
| |
SR | System remote controller | 50 | groups, 50 | indoor units | |
|
|
|
|
| |
AN | ON/OFF remote controller | 16 | groups, 50 | indoor units | |
|
|
|
|
| |
SC | System controller | 50 | groups, 50 | indoor units | |
|
|
|
|
|
32