(7)Notes on charge system

If there is a group that is not set in the charge block, the electric power amount for that group will not be included in the air-conditioning charge. If there are groups which require charging to be divided, set those groups as operation blocks or charge blocks to accomplish this.

The air conditioning charge can be calculated by block units or by power meter units. Note that even when OA processing unit, LOSSNAY, A control unit or K control unit are included in the block setting, they are not included in the air conditioning charge of the block unit.

The function for Charge calculation (Without WHM connection) is only applicable to the indoor unit. It does not apply to OA processing unit, LOSSNAY, A control unit, and K control unit, etc.

Some older M-NET control indoor units are not compatible with the charge function.

When the system is changed or the air conditioner is extended, which may require address changes, the charge calculation may be affected in some cases.

Executing such changes or extensions are recommended after gaining approval from the building owner(s).

(8)Charging (Billing) restrictions

The air conditioning cost calculation method use by this integrated software TG -2000A is the Mitsubishi proprietary general electric power apportioning method. Thus, it is not calculated using watt hour meters installed at the power supply to each unit. Additionally, it cannot be employed in applications demanding calculations based on watt hour meters installed at each unit. Thus when using this unit, we recommend a separate contract be established between the building owner and the tenant that specifies “air conditioning fees will be collected based on proport ional usage (including special considerations for downtime).”

(9)Function description

The function/specifications may partially change and improvements may be made without any notice.

2.4Other Devices

Other devices specified or recommended for use with the TG -2000A are listed below.

N a m e

 

Manufacturer

 

Model

Notes

 

 

 

 

 

 

 

 

Printer

(None specified)

(None specified)

Supports a page printer only

 

 

 

 

 

(Must run under the OS used

 

 

 

 

 

(Windows 2000/XP Professional).)

Watt hour meter

1

Northern Design

1

POWER RAIL 323 +

Only supports RS -485 output of

 

 

(Electronics) Ltd.

 

OPTION Module

the specified model and

 

2

Elcomponent

2

AEM31D/485

manufacturer

 

 

Limited

3 CVM-BC-ITF-RS485-

 

 

3

CIRCUTOR

 

C2

 

 

4

elcontrol energy

4

ED39din 485

 

RS -232C/

(None specified)

(None specified)

Necessary when measuring the

RS -485

 

 

 

 

electric power.

converter

 

 

 

 

Ex) B&B Electronics Model

 

 

 

 

 

485DRJ

 

 

 

 

 

Black Box Model IC520A -F or

 

 

 

 

 

IC108A

 

 

 

 

 

* Regarding watt hour meter 2,

 

 

 

 

 

the converter from the manu-

 

 

 

 

 

facturer may also emit light.

 

 

 

 

UPS

(None specified)

(None specified)

Installation is recommended to

(Uninteruptable

 

 

 

 

prevent destruction or loss of

power supply)

 

 

 

 

billing (Charge data) and other

 

 

 

 

 

data. (Any type suitable for use

 

 

 

 

 

with personal computers)

4

Image 7
Contents Please keep this manual for future use Please read this manual before using the unitContents Page Other machines Safety PrecautionsDo not use with other applications Compatible Units System Requirements Requirements system recommendations¡ *1 Number of units RestrictionsRestrictions M e Manufacturer Model Other DevicesHardware Connection Diagram System Configuration System Configuration Example50A test run Flow of Site AdjustmentTools for Site Adjustment PC connections and settingsD e l s IP address range Test operation from centralized controller G-50APage Steps Action Details How to InstallationG-2000A Setup Preparing for installationWhen the installation is completed, restart the computer Running TG-2000A Setup New setupMsde setup Database setupRead the license agreement Check the installation folderInstallation start confirmation TG-2000A setup completionTG-2000A uninstall G-2000A UninstallMsde uninstall Part Names and Functions Window Elements Shift from the control window to the initial window Accessing Functions and Moving between WindowsBasic Mouse Operation Shift from the initial window to the control windowPage Page User Set -up Set TG -2000A functions Page Page Startup Initial Startup and Shutdown Before StartupTG-2000A Shutdown ShutdownShutting down the OS System Setting Procedure System Setting Procedure System Setting ScreenGeneral Operation User Set-upReliability Function Connection SettingSite Name Set-up Energy Monitoring RelatedPage IP address of G-50A se t-up Step Setting Procedure and RestrictionsG-50 Connection Set-up Number of G-50A se t-up StepMonitor the optional functions being used. Procedure System Configuration Set-upUnit composition set-up Step 2 G-50A data collection StepIcon Name Address range Change the unit configuration. ProcedureSe t-up of refrigerant system Step Set-up of group Step Interlocking destination un-set unit Interlocked setting StepChange the group No. Procedure Interlocking ventilation unitMonitoring Screen Set-up Configuration Procedure and RestrictionsSet-up of model name Step Set-up of the number of floors, and floor name Step Set-up of floor name and G -50 Creation of a plane view StepGroup List Set-up of icon arrange and name StepFloor Selection Display Button Set the group icons on each floor and set their namesName Change button Block Set button Release button Set the block groups. ProcedureDeleting block settings Set-up of block StepChanging the block name Check before WHM setup. Procedure Setting Procedures and RestrictionsModel Baud rate Parity Stop bit Energy Monitoring S e t-up Set Charge System options. ProcedureProportiona l division reference data Division mode StepDivision mode for outdoor unit Division mode for indoor unitDelete Watt Hour Meter Relationships Select the OC icon, and click on the selected outdoor unitSet the Indoor Unit and Watt Hour Meter Relationship Relation between indoor units and watt hour meters StepDeleting Watt Hour Meter Relationships Charge Blocks Step Set the charge blocks. ProcedureRelease a block from charge blocks Delete the charge blockAdd charge blocks Set the electric power rate schedule. Procedure Selecting a Currency from the Display ProcedureManually Setting the Currency Exit the Currency Settings10Standard charge set Step Set the standard charge . ProcedureSet the date/time . Procedure Function ContentsTime Set-up Monitor button Monitor the timeChange the password Password S e t-upNo repair is required Overview Remarks Display the Maintenance screen. Procedure Maintenance of Charge DataPreparing for Charging Data Maintenance Maintenance Methods and RestrictionsMaintaining Apportioned Unit Data Unit Data MaintenanceCorrection method Maintenance example Maintaining watt hour Meter Data Procedure Watt Hour Meter Data MaintenanceOperation Amount Data Monitoring Watt hour Meter Monitor Function ProcedureDescription of function Monitoring operation amount data Charge Parameter OutputMonitor the data for the last day after Output file data format Charging RemedyPerforming charging remedy Preparation Preparing to perform charging remedyApportioning integrated Remark InterVal Remedial apportioning setting screenRemedial apportioning confirmation screen Calculating screen Remedy when personal computer HDD fails no backup Remedy when personal computer HDD fails backup Day before recovery day Apportioning method when computer crashes Remedy when watt hour meter fails monitoring impossible Integrate d Remedy for system information setting error Total air-conditioning charge including that Air-conditioning unit error codes Error Code ListPage Page System error codes Setting item Case Setting Check ListDetail of function Test run check sheet Test Run CheckLRC Date Tester Charging No WHM connection Test Run Check Charging Test Run CheckTest item Comment Page Capacity Total Division mode Charge settingSetting Check Within OutsideExample 1100 conditioner 1300 Outside Within 12001400 Page Page WHM1 WHM2 WHM3 WHM4 WHM5 WHM6 Memo What you need Appendix 1 Installing Windows XP ProfessionalSetup Procedure Preparing for Se tupPage Windows XP Appendix 2 Auto Log-in Confirmation MethodWindows Page WT03901X01