Mitsubishi Electronics TG-2000A G-50 Connection Set-up, Setting Procedure and Restrictions

Page 30

8.5G-50 Connection Set-up

Set the integrated centralized control software TG-2000A, number of G-50A units connected, and the IP address. It is possible for this setting to monitor and display the option functions state of the G-50A.

8.5.1 Setting Procedure and Restrictions

Confirm the precautions and procedure before setting the G-50A connection.

Perform the check before setting the G-50A connection. [Procedure]

1)Select the [G-50 connection set -up] button. Click the [G-50 connection set-up] button located in the system setting group on the initial window.

2)Select the [ON] button after confirming the display contents.

Check the contents of the alarm displayed. When there are not any problems found, click the [OK] button to advance to the setting.

*When the [Cancel] button is clicked, this setting is terminated to return to the initial screen.

Set the G-50A connection in accordance with the

following procedure.

Step 1: Number of G-50 set -upG-50 connection Set-up

Step 2: IP address of G-50 set -up

8.5.2 Number of G-50A se t-up (Step 1)

Set the number of G-50 connected to the system.

S e t-up the number of G-50A [Procedure]

1)Click the “/ “ buttons .

Use the “/ “ buttons to set the number of G-50A. Number of connectable G-50A units: 1 to 40 units

2)Click [OK] button.

When finished making settings, click the [OK] button.

*When the [Cancel] button is clicked, this setting is terminated to return to the initial window.

Number of G-50A set-up

8.5.3 IP address of G-50A se t-up (Step 2)

Set the data of the G-50A IP address connected to the data of the integrated centralized control software.

Register the G-50A IP address. [Procedure]

1)Select the G-50 No. with the “/ “ buttons. In this case, use the “ / “ buttons to select the G-50A No. for which the IP address information is registered.

IP address of G-50A set -up

27

Image 30
Contents Please read this manual before using the unit Please keep this manual for future useContents Page Safety Precautions Other machinesDo not use with other applications System Requirements Requirements system recommendations Compatible Units¡ *1 Restrictions Number of unitsRestrictions Other Devices M e Manufacturer ModelSystem Configuration System Configuration Example Hardware Connection DiagramPC connections and settings Flow of Site AdjustmentTools for Site Adjustment 50A test runTest operation from centralized controller G-50A D e l s IP address rangePage Preparing for installation InstallationG-2000A Setup Steps Action Details How toDatabase setup Running TG-2000A Setup New setupMsde setup When the installation is completed, restart the computerTG-2000A setup completion Check the installation folderInstallation start confirmation Read the license agreementG-2000A Uninstall TG-2000A uninstallMsde uninstall Part Names and Functions Window Elements Shift from the initial window to the control window Accessing Functions and Moving between WindowsBasic Mouse Operation Shift from the control window to the initial windowPage Page User Set -up Set TG -2000A functions Page Page Initial Startup and Shutdown Before Startup StartupShutdown TG-2000A ShutdownShutting down the OS System Setting Procedure System Setting Screen System Setting ProcedureUser Set-up General OperationConnection Setting Reliability FunctionEnergy Monitoring Related Site Name Set-upPage Number of G-50A se t-up Step Setting Procedure and RestrictionsG-50 Connection Set-up IP address of G-50A se t-up StepSystem Configuration Set-up Monitor the optional functions being used. Procedure2 G-50A data collection Step Unit composition set-up StepChange the unit configuration. Procedure Icon Name Address rangeSe t-up of refrigerant system Step Set-up of group Step Interlocking ventilation unit Interlocked setting StepChange the group No. Procedure Interlocking destination un-set unitConfiguration Procedure and Restrictions Monitoring Screen Set-upSet-up of model name Step Set-up of the number of floors, and floor name Step Creation of a plane view Step Set-up of floor name and G -50Set the group icons on each floor and set their names Set-up of icon arrange and name StepFloor Selection Display Button Group ListSet-up of block Step Set the block groups. ProcedureDeleting block settings Name Change button Block Set button Release buttonChanging the block name Setting Procedures and Restrictions Check before WHM setup. ProcedureModel Baud rate Parity Stop bit Set Charge System options. Procedure Energy Monitoring S e t-upDivision mode for indoor unit Division mode StepDivision mode for outdoor unit Proportiona l division reference dataSelect the OC icon, and click on the selected outdoor unit Delete Watt Hour Meter RelationshipsRelation between indoor units and watt hour meters Step Set the Indoor Unit and Watt Hour Meter RelationshipDeleting Watt Hour Meter Relationships Set the charge blocks. Procedure Charge Blocks StepDelete the charge block Release a block from charge blocksAdd charge blocks Exit the Currency Settings Selecting a Currency from the Display ProcedureManually Setting the Currency Set the electric power rate schedule. ProcedureSet the standard charge . Procedure 10Standard charge set StepFunction Contents Set the date/time . ProcedureTime Set-up Monitor the time Monitor buttonPassword S e t-up Change the passwordNo repair is required Overview Remarks Maintenance Methods and Restrictions Maintenance of Charge DataPreparing for Charging Data Maintenance Display the Maintenance screen. ProcedureUnit Data Maintenance Maintaining Apportioned Unit DataCorrection method Maintenance example Watt Hour Meter Data Maintenance Maintaining watt hour Meter Data ProcedureWatt hour Meter Monitor Function Procedure Operation Amount Data MonitoringDescription of function Charge Parameter Output Monitoring operation amount dataMonitor the data for the last day after Charging Remedy Output file data formatPerforming charging remedy Preparing to perform charging remedy PreparationRemedial apportioning setting screen Apportioning integrated Remark InterValRemedial apportioning confirmation screen Calculating screen Remedy when personal computer HDD fails no backup Remedy when personal computer HDD fails backup Day before recovery day Apportioning method when computer crashes Remedy when watt hour meter fails monitoring impossible Integrate d Remedy for system information setting error Total air-conditioning charge including that Error Code List Air-conditioning unit error codesPage Page System error codes Setting Check List Setting item CaseDetail of function Test Run Check Test run check sheetLRC Date Tester Charging Test Run Check Charging No WHM connection Test Run CheckTest item Comment Page Capacity Check Within Outside Division mode Charge settingSetting TotalExample 1100 conditioner 1300 Outside Within 12001400 Page Page WHM1 WHM2 WHM3 WHM4 WHM5 WHM6 Memo Preparing for Se tup Appendix 1 Installing Windows XP ProfessionalSetup Procedure What you needPage Appendix 2 Auto Log-in Confirmation Method Windows XPWindows Page WT03901X01