11.3.2 Proportionally Divided Power Charge (RS-485 WHM connection) Test Run Check

Charging test run check sheet (proportionally divided power charge (RS-485 WHM connection)) Perform the charging test run check after the test run check is complete.

Follow the order of testing prescribed by the charging test run check sheet and check the following items: (1) to (8).

Note:

When the results do not conform to the judgment standards outlined in (7), fix the problem and restart the check from (1).

(1)Check the charge setting details on the man-machine console.

Write the charge setting details down on the charging test run check sheet. Check the details of the data to ensure charging is operating correctly.

Division mode selection (See section 8.9.2)

￿Set the mode used.

Charge setting (See section 8.9.9)

￿Set the time using the with within/outside setting to perform the charging test run check. (Same unit cost for the With daytime/nighttime setting, Without weekend charge setting, and Without seasonal charge setting)

For the unit cost, set both within and outside to 10.

Execute the setting so that the test run time for the air conditioner is carried over both within and outside.

 

 

Test run period of air

 

 

 

 

Example) 11:00 conditioner

13:00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outside

 

Within

 

Outside

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12:0014:00

Standard charge setting (See section 8.9.10)

àFor charging test run check purposes, set “10,000”.

Settlement day setting (See Management manual section 9.3).

àFor charging test run check purposes, set it to the next day

Charge block setting (See section 8.9.7)

àSet the charge block to be manipulated

*To set the charge block, (operat ion) block must be set. (See section 8.7.7)

Check the following details for each indoor unit.

Addresses of the outdoor units in the same refrigeran system (See section 8.6.4)

Which indoor units correspond to each watt hour meter (See section 8.9.5)

Performance of indoor units (See section 8.9.6)

Fan capacity (See section 8.9.6)

*The number of items to be confirmed depends on the charge apportioning method (mode).

Check the following details for each outdoor unit.

Which outdoor units correspond to each watt hour meter. (See section 8.9.3)

Capacity of crank case heater (See section 8.9.4)

(If using the Super Y series, include the crank case heater capacity of the subsidiary outdoor unit (OS).)

*The number of items to be confirmed depends on the charge apportioning method (mode).

Check the following details for watt hour meter.

Address (See section 8.8.2)

Maximum integrated value (See section 8.8.3)

*For Without WHM connection, the set contents do not have to be checked.

Note:

Always ensure the details of each setting are correct. (Incorrect setting details will affect air-conditioning charging.)

86

Image 89
Contents Please keep this manual for future use Please read this manual before using the unitContents Page Do not use with other applications Safety PrecautionsOther machines ¡ *1 System Requirements Requirements system recommendationsCompatible Units Restrictions RestrictionsNumber of units M e Manufacturer Model Other DevicesHardware Connection Diagram System Configuration System Configuration ExampleTools for Site Adjustment Flow of Site AdjustmentPC connections and settings 50A test runD e l s IP address range Test operation from centralized controller G-50APage G-2000A Setup InstallationPreparing for installation Steps Action Details How toMsde setup Running TG-2000A Setup New setupDatabase setup When the installation is completed, restart the computerInstallation start confirmation Check the installation folderTG-2000A setup completion Read the license agreementMsde uninstall G-2000A UninstallTG-2000A uninstall Part Names and Functions Window Elements Basic Mouse Operation Accessing Functions and Moving between WindowsShift from the initial window to the control window Shift from the control window to the initial windowPage Page User Set -up Set TG -2000A functions Page Page Startup Initial Startup and Shutdown Before StartupShutting down the OS ShutdownTG-2000A Shutdown System Setting Procedure System Setting Procedure System Setting ScreenGeneral Operation User Set-upReliability Function Connection SettingSite Name Set-up Energy Monitoring RelatedPage G-50 Connection Set-up Setting Procedure and RestrictionsNumber of G-50A se t-up Step IP address of G-50A se t-up StepMonitor the optional functions being used. Procedure System Configuration Set-upUnit composition set-up Step 2 G-50A data collection StepIcon Name Address range Change the unit configuration. ProcedureSe t-up of refrigerant system Step Set-up of group Step Change the group No. Procedure Interlocked setting StepInterlocking ventilation unit Interlocking destination un-set unitSet-up of model name Step Configuration Procedure and RestrictionsMonitoring Screen Set-up Set-up of the number of floors, and floor name Step Set-up of floor name and G -50 Creation of a plane view StepFloor Selection Display Button Set-up of icon arrange and name StepSet the group icons on each floor and set their names Group ListDeleting block settings Set the block groups. ProcedureSet-up of block Step Name Change button Block Set button Release buttonChanging the block name Check before WHM setup. Procedure Setting Procedures and RestrictionsModel Baud rate Parity Stop bit Energy Monitoring S e t-up Set Charge System options. ProcedureDivision mode for outdoor unit Division mode StepDivision mode for indoor unit Proportiona l division reference dataDelete Watt Hour Meter Relationships Select the OC icon, and click on the selected outdoor unitDeleting Watt Hour Meter Relationships Relation between indoor units and watt hour meters StepSet the Indoor Unit and Watt Hour Meter Relationship Charge Blocks Step Set the charge blocks. ProcedureAdd charge blocks Delete the charge blockRelease a block from charge blocks Manually Setting the Currency Selecting a Currency from the Display ProcedureExit the Currency Settings Set the electric power rate schedule. Procedure10Standard charge set Step Set the standard charge . ProcedureTime Set-up Function ContentsSet the date/time . Procedure Monitor button Monitor the timeChange the password Password S e t-upNo repair is required Overview Remarks Preparing for Charging Data Maintenance Maintenance of Charge DataMaintenance Methods and Restrictions Display the Maintenance screen. ProcedureMaintaining Apportioned Unit Data Unit Data MaintenanceCorrection method Maintenance example Maintaining watt hour Meter Data Procedure Watt Hour Meter Data MaintenanceDescription of function Watt hour Meter Monitor Function ProcedureOperation Amount Data Monitoring Monitor the data for the last day after Charge Parameter OutputMonitoring operation amount data Performing charging remedy Charging RemedyOutput file data format Preparation Preparing to perform charging remedyApportioning integrated Remark InterVal Remedial apportioning setting screenRemedial apportioning confirmation screen Calculating screen Remedy when personal computer HDD fails no backup Remedy when personal computer HDD fails backup Day before recovery day Apportioning method when computer crashes Remedy when watt hour meter fails monitoring impossible Integrate d Remedy for system information setting error Total air-conditioning charge including that Air-conditioning unit error codes Error Code ListPage Page System error codes Detail of function Setting Check ListSetting item Case Test run check sheet Test Run CheckLRC Date Tester Test item Comment Charging Test Run CheckCharging No WHM connection Test Run Check Page Capacity Setting Division mode Charge settingCheck Within Outside TotalExample 1100 conditioner 1300 Outside Within 12001400 Page Page WHM1 WHM2 WHM3 WHM4 WHM5 WHM6 Memo Setup Procedure Appendix 1 Installing Windows XP ProfessionalPreparing for Se tup What you needPage Windows Appendix 2 Auto Log-in Confirmation MethodWindows XP Page WT03901X01