I. PROGRAM LOCATION 06 (PL06)
LO Temp cool down temperature/time
PL06
LOCd
Perm Press
·
100
·
2HI Temp
Perm Press
LO Temp
Refer to
Section V
for instructions
on entering program locations.
(Wait 3-Seconds)
100
·
2
LO Temp HI Temp
Perm Press
PL07
Proceed to next location
to be changed To exit program mode,
open program switch
Location to be viewed/changed.
Press “Perm Press” key.
Display will read “LOCd,” LO Temp
cool down status for 3-seconds and then
the actual temperature and time
programmed. If no changes, press “Perm
Press” key twice, otherwise press “HI” or
“LO” keys and then “Perm Press” key.
Temperature Decrease Temperature Increase
Time Decrease Time Increase
Summary: Cool down temperature is programmable from a minimum of 70° F to a maximum of 190° F in ten
degree increments or from a minimum 21° C to a maximum of 88° C in five-degree increments.
For the AD-26 and AD-295 any three (3) of the selections (HI/LO/PP) are programmable from a
minimum of 100° F to a maximum of 170° F in ten-degree increments or from a minimum of 38° C
to a maximum of 77° C in five-degree increments.
For the AD-540 and WDA-540 any three (3) of the selections (HI/LO/PP) are programmable
from a minimum of 100° F to a maximum of 160° F in ten-degree increments or from a minimum of
38° C to a maximum of 71° C in five-degree increments.
Cool down is programmable from 0 to 9 minutes.