Serial and network connected UPSes must first be connected to, and configured to communicate with the console server:

For serial UPSes attach the UPS to the selected serial port on the console server. From the Serial and Network: Serial Port menu, configure the Common Settings of that port with the RS-232 properties, etc. required by the UPS (refer to Chapter 5.1.1—Common Settings). Then select UPS as the Device Type.

For each network connected UPS, go to the Serial & Network: Network Hosts menu and configure the UPS as a connected Host by specifying it

as Device Type: UPS and clicking Apply.

No such configuration is required for USB connected UPS hardware.

Figure 8-7. UPS connections.

Select the Serial & Network: UPS Connections menu. The Managed UPSes section will display all the UPS connections that have already been configured.

Click Add Managed UPS.