Security Escort Technical Reference Manual 3.0 System Menus and Screens

EN 38

No Restriction: This selection typically is left at this setting at all times. The output is not restricted by an individual transponder.

Only From Transponder Selected: The selected events are only output if they were reported from the transponder selected in the Transponder Restriction above.

All from Transponder Selected: All events are reported from the transponder selected in the Transponder Restriction above. The selected events are reported from all other transponders in the system.

Alarms

Outputs the information about an alarm including location, but not the transponder and receiver levels. This is the data typically sent to a printer.

Points, Reporting Alarm

Outputs the transponder and receiver levels for an alarm. Typically, this is the data too detailed to send to a printer and is used for diagnostics, not normal system operation.

Tests, Single Line

Outputs the simple information about a test. Typically, this is the data normally sent to a printer.

Tests Including Point Info

Outputs the transponder and receiver levels for a test. This is the data usually too detailed to send to a printer and is used for diagnostics, not normal system operation. If this option is selected, Test, Single Line above, would not be selected for the same output device.

Transmitter Low Battery

Outputs low battery reports received from transmitters.

Operator Activity Log

Outputs all other operator activity (audit trail) not covered by specific event selections.

Preferences Changes

Outputs all changes made to system preference selections.

Database Backup and Restore

Records all database backup and restore activity.

Operator Database Changes

Records all changes to the operator database.

Subscriber Database Changes

Records all changes to the subscriber database.

Transponder Database Changes

Records all changes to the transponder database.

Spare 2

Not currently implemented. Leave unchecked.

Report Database Changes

Records all changes to the Alarm Report Database.

Communications Failure

Records all communication failures and restorals.

Transponder Communication

Records all communications to transponders. This selection is only used for engineering diagnostics. Leaving this item selected generates a significant amount of history and fills up the hard disk drive quickly. Leave this item unchecked.

Supervision Monitor

Reports changes in the supervision status for all transmitters that are being supervised.

RF Point Troubles

Outputs all troubles reported by RF points. Check this item to monitor problems with RF points.

Transponder Maps

Outputs all transponder status maps. This selection is only used for diagnostics. Leave this item unchecked.

Receive Level Maps

Outputs all maintenance alarm receive level maps. This selection is only used for diagnostics. Leave this item unchecked.

Database Errors

Outputs all reported database errors. This item is checked.

Transponder Troubles

Outputs all reported transponder troubles. This item is checked for devices used to monitor problems.

Bosch Security Systems 6/12 38947D

Page 38
Image 38