7-7

Cisco MGX 8220 Installation and Configuration
Release 5.0, Part Number 78-6430-03 Rev. D0, November 2003
Chapter Rack-Mounting the MGX 8220 Units

The equipment should be mounted in the rack to prevent any hazardous condition due to uneven

mechanical loading.

Cooling Configuration Guidelines

To ensure that the MGX 8220 switch gets proper ventilation and is cooled properly, you must adhere to

the following cooling configur at io n guidelines:

You must never have more than four (4) s h elve s installed between the a ir in let and the air exhaust.

The main cooling module by itself can only push enough air to cool one or two shelves.

If you are using three or four shelves , you mu st insta ll a boos ter co oling mo dule be tween th e second

and third shelves.

The inlet and exhaust areas must be unrestricted . Re strictive doors over the front or the rear of the

unit are not allowed.

Figure7-2 Rack-Mounted MGX 8220—One- and Two- Shelf Configurations

17.750"
minimum
17.750"
minimum
1.75" (spacer)
or
3.5" (plenum)
1 or 2 U
1.75"
or
3.5"
1 or 2 U
5 1/4"
3 U
5 1/4"
3 U 5 1/4"
3 U
5 1/4"
3 U
8.75"
5 U
8.75"
5 U
8.75"
5 U
AC power module
(if used)
Main cooling
module
12345678910111213141516
Plenum or spacer
AC power module
(if used)
Main cooling
module
12345678910111213141516
12345678910111213141516
MGX 8220 shelf
MGX 8220 shelfMGX 8220 shelf
Plenum or spacer
H8275