Chapter 1 Basic Troubleshooting Tasks and Startup Issues

Displaying System Environment Information

Displaying System Environment Information

Use the show environment command to display the basic system environment status, to verify the following:

Make sure the system operating temperature is equal to or less than 41° F at the inlet and 104° F degrees at the core (5° C and 40° C).

That the fan assembly module is installed in the chassis and operating properly.

Report the operational status of the PEMs and blower

If the operating temperature is not between 41° F and 104° F, refer to the “Fan Assembly Module Faults” section on page 2-7.

The following example is sample output from the show environment command for a system with two DC PEMs installed:

UBR10K-ROUTER1# show environment

Temperature

normal:chassis inlet measured at 29C/84F

Temperature

normal:chassis core measured at 39C/98F

Fan: OK

 

 

 

Power Entry

Module 0 type DC status:

OK

Power Entry

Module 0 Power:

555w

Power Entry

Module 0

Voltage:

62v

Power Entry

Module 1

type DC status:

OK

Power Entry

Module 1

Power:

558w

Power Entry

Module 1

Voltage:

62v

UBR10K-ROUTER1#

Hardware Troubleshooting Flowchart

Use Figure 1-1to determine which component of your Cisco uBR10012 router is malfunctioning. Figure 1-1describes a series of hardware dependent startup events that must take place for a

Cisco uBR10012 router to allow the passage of IP traffic. At each main point of the flowchart, there are pointers to the chapters in this guide that describe how to troubleshoot individual pieces of hardware.

Note This flowchart does not address software configuration problems.

Cisco uBR10012 Universal Broadband Router Troubleshooting Guide

1-4

OL-1237-01

 

 

Page 16
Image 16
Cisco Systems UBR10012 manual Displaying System Environment Information, Hardware Troubleshooting Flowchart