78 Installing System Components
NOTICE: To ensure proper system cooling, the power supply blank must be
installed on the unoccupied power supply bay in a non-redundant configuration.
See "Installing the Power Supply Blank" on page80.
Removing a Power Supply
NOTICE: The system requires one power supply to operate the system normally. On
power-redundant systems, remove and replace only one power supply at a time in a
system that is powered on.
NOTE: On your rack system, you may have to unlatch and lift the optional cable
management arm if it interferes with power supply removal. For information about
the cable management arm, see the system’s Rack Installation Guide.
1
If your system has a single power supply, turn off the system and all
attached peripherals. For a redundant system, you can leave the system
running and proceed to the next step.
2
Disconnect the power cable from the power source.
3
Disconnect the power cable from the power supply and remove the cable
from the cable retention bracket.
4
Release the locking tab on the left side of the power supply by pressing in
toward the right, and rotate the power-supply handle up until the power
supply is released from the chassis. See Figure3-7.
5
Pull the power supply straight out to clear the chassis.