OPERATION

Table 3. User Settings (continued)

Description

Available Settings

Default Setting

 

 

 

Frequency Converter

[Enabled] [Disabled]

Disabled

 

If Enabled, the UPS operates as a frequency

 

 

converter, with bypass operation and all

 

 

bypass-related alarms disabled.

 

 

 

 

Overload Alarm Level

[10%] [20%] [30%] ... [100%]

100%

 

These values affect alarm level only, not UPS

Generates the Output Overload

 

operation such as transfers or shutdown.

alarm at the set level.

 

 

 

Transfer to Bypass When Overload*

[Immediate] [After Delay]

Immediate

 

If Immediate, transfer occurs at load >102%.

 

 

If After Delay, transfer occurs according to

 

 

Table 19 on page 84.

 

 

 

 

Power Strategy

[Normal] [High Efficiency]

Normal

 

See “Setting Power Strategy” on page 48.

 

 

 

 

Automatic Start Delay

[Disabled] [No Delay] [1s] [2s]...[32767s]

Load Segment 1: No Delay

 

If Disabled, automatic restart is not allowed.

Load Segment 2: No Delay

 

See “Configuring Load Segments” on page 49.

 

 

 

 

Automatic on Battery Shutdown

[Disabled] [No Delay] [1s] [2s]...[32767s]

Load Segment 1: Disabled

 

Shutdown cancels if utility returns before the

Load Segment 2: Disabled

 

delay expires. See “Configuring Load

 

 

Segments” on page 49.

 

 

 

 

Start on Battery

NOTE Utility must be present and output enabled at initial UPS startup.

[Enabled] [Disabled]

Enabled

After initial startup, battery voltage must

 

exceed 2.10 volts per cell to start on battery.

 

Energy Saving Mode

[Disabled] [50W] [100W] ... [1000W]

Disabled

 

UPS output is turned off if the UPS is on

 

 

battery and output power is below the

 

 

selected level.

 

 

 

 

Remote Shutdown Delay

[No Delay] [1s] [2s]...[10800s]

No Delay

 

 

 

Delayed Shutdown Delay

[No Delay] [1s] [2s]...[10800s]

120s

 

 

 

Behavior on Rectifier Input Loss

NOTE Available only in >3000 VA UPSs with separate supply sources for the rectifier and bypass inputs.

[Prefer Battery] [Prefer Bypass]

Prefer Battery

If Prefer Bypass, upon loss the UPS will

 

transfer to bypass in 3 seconds and remain as

 

long as bypass is available.

 

On Battery Notice Delay

[0] [1s] [2s]...[99s]

5s

 

 

 

* See “Configuring Bypass Settings” on page 48.

Eaton® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com

41

Page 49
Image 49
Eaton Electrical 9130 manual Frequency Converter Enabled Disabled