OPERATION

UPS Shutdown

To shut down the UPS:

1.Press the button on the front panel for three seconds.

The UPS starts to beep and shows a status of “UPS off pending...”.

The UPS then transfers to Standby mode, and the indicator turns off.

NOTE Releasing the button before three seconds returns the UPS to its original operating mode.

2.Switch off utility power where the UPS is connected.

ÊTransferring the UPS Between Modes

From Normal to Bypass Mode. Press any button to activate the menu options, then select CONTROL and GO TO BYPASS.

From Bypass to Normal Mode. Press any button to activate the menu options, then select CONTROL and GO TO NORMAL.

ÊRetrieving the Event Log

To retrieve the Event Log through the display:

1.Press any button to activate the menu options, then select

EVENT LOG.

2.Scroll through the listed events.

To retrieve the Event Log through the serial port:

1.From the communication device connected to the serial port, send one of the following command sequences: ESC-L (ASCII characters 27 and 76) or ESC-I (ASCII characters 27 and 108).

The UPS returns a header containing the UPS identification (UPS type, part number, and serial number), firmware version, and the current date and time, followed by the event history.

2.Use the connected communication device to view or print the information. The report is delivered in ASCII format.

Eaton® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com