SPECIFICATIONS
Table 19. Electrical Output (All Models)
| All Models | Normal Mode | Battery Mode | 
| 
 | 
 | 
 | 
| Voltage Regulation | ±2% | Nominal output voltage ±3% | 
| 
 | 
 | 
 | 
| Efficiency | >95% (High Efficiency mode), >88% | >79.5% (700 VA), | 
| 
 | 
 | >82%  | 
| 
 | 
 | >84%  | 
| 
 | 
 | 
 | 
| Frequency Regulation | Sync with line ±3 Hz of nominal line | ±0.1 Hz of  | 
| 
 | frequency (outside this range: | frequency | 
| 
 | ±0.1 Hz of  | 
 | 
| 
 | frequency) | 
 | 
| 
 | 
 | 
 | 
| 
 | Low Voltage Models | High Voltage Models | 
| 
 | 
 | 
 | 
| Nominal Outputs | 100/110/120/127V | 200/208/220/230/240V | 
| 
 | (voltage configurable or | (voltage configurable or | 
| 
 | ||
| 
 | 1000/1500/2000/3000 VA | 1000/1500/2000/3000 VA | 
| 
 | 0.9/1.35/1.8/2.7 kW | 0.9/1.35/1.8/2.7 kW | 
| 
 | 
 | |
| Frequency | 50 or 60 Hz, autosensing or configurable as a frequency converter | |
| 
 | 
 | |
| Output Overload (Normal Mode) | ||
| 
 | ||
| 
 | ||
| 
 | >150%: Load transfers to Bypass mode after 100 ms. (Level 4) | |
| 
 | NOTE Default configuration transfers immediately to Bypass at >102%. | |
| 
 | 
 | |
| Output Overload (Bypass Mode) | ||
| 
 | ||
| 
 | ||
| 
 | >150%: UPS shuts down after 300 ms. (Level 4) | |
| 
 | 
 | |
| Output Overload (Battery Mode) | ||
| 
 | ||
| 
 | ||
| 
 | >150%: UPS shuts down after 100 ms. (Level 4) | |
| 
 | 
 | 
 | 
| Voltage Waveform | 
 | Sine wave | 
| 
 | 
 | |
| Harmonic Distortion | <3% THD on linear load; <5% THD on  | |
| 
 | 
 | |
| Transfer Time | Online mode: 0 ms (no break) | |
| 
 | High Efficiency mode: 5 ms maximum (due to loss of utility) | |
| 
 | 
 | 
 | 
| Power Factor | 
 | 0.9 | 
| 
 | 
 | 
 | 
| Load Crest Factor | 
 | 3 to 1 | 
| 
 | 
 | 
 | 
| 84 | Eaton® 9130 UPS  | 