COMMUNICATION

Relay Output Contacts

The UPS incorporates three programmable relay outputs with potential free contacts for remote alarm indications: a standard relay port and two outputs in the RS-232 communication port. See Figure 18 on page 53 for the locations of the ports. An additional four relay outputs can be obtained with the compatible Relay Interface Card.

Configure the relay outputs with the “Relay Configuration” setting in “User Settings” on page 40.

W A R N I N G

The relay output contacts must not be connected to any utility connected circuits. Reinforced insulation to the utility is required. The relay output contacts have a maximum rating of

30 Vac/1A and 60 Vdc/2A nominal values.

Table 5 shows the options for the relay output contacts.

Table 5. Relay Output Configuration Options

Signal

Description

 

 

UPS ok

Activated when the UPS is feeding the load on inverter or on

 

bypass and no alarms are active

 

 

On Bypass

Activated when the UPS is NOT on bypass operation

 

 

On Battery

Activated when the UPS operates on battery and the “On

 

Battery Notice Delay” time has expired

 

 

Battery Low

Activated with the “Battery Low” alarm according to the

 

“Battery Low Alarm” setting

 

 

Ext. Charger On

Controls an optional external battery charger on and off

 

 

Figure 22 shows a schematic of the relay output contacts.

1Normally Open

2 Normally Closed

3 Common

Relay Output

Figure 22. Standard Relay Port Connections

58

Eaton® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com

Page 66
Image 66
Eaton Electrical 9130 manual Relay Output Contacts, Relay Output Configuration Options, Signal Description