Eaton Electrical 9130 manual Bypass Mode

Models: 9130

1 120
Download 120 pages 22.21 Kb
Page 52
Image 52

OPERATION

If battery capacity becomes low while in Battery mode, the indicator flashes slowly and the audible alarm beeps once every second. If the “Battery Low” alarm is set, the indicator also illuminates solid. This warning is approximate, and the actual time to shutdown may vary significantly.

NOTE Depending on the UPS load and the number of Extended Battery Modules (EBMs) connected, the “Battery Low” warning may occur before the batteries reach 25% capacity. See Table 23 on page 88 for estimated runtimes.

When utility power is restored after the UPS shuts down, the UPS automatically restarts.

Bypass Mode

In the event of a UPS overload or internal failure, the UPS transfers your equipment to utility power. Battery mode is not available and your equipment is not protected; however, the utility power continues to be

passively filtered by the UPS. The indicator illuminates.

The UPS remains in Bypass mode for at least 5 seconds (if the bypass source remains acceptable). If three transfers to Bypass occur within 10 minutes for any reason other than user command, the UPS locks in Bypass for 1 hour or until any control button is pressed.

The UPS transfers to Bypass mode when:

SThe user activates Bypass mode through the front panel.

SThe UPS detects an internal failure.

SThe UPS has an overtemperature condition.

SThe UPS has an overload condition listed in Table 19 on page 84.

NOTE The UPS shuts down after a specified delay for overload conditions listed in

Table 19 on page 84. The UPS remains on to alarm the fault.

44

Eaton® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com

Page 52
Image 52
Eaton Electrical 9130 manual Bypass Mode