SPECIFICATIONS

Table 23. Battery Runtimes (in Minutes) at 100% Load (Rack Models)

Model

Internal Batteries

+ 1 EBM

+ 2 EBMs

+ 3 EBMs

+ 4 EBMs

 

 

 

 

 

 

PW9130L700R-XL2U

9

41

72

105

130

 

 

 

 

 

 

PW9130L1000R-XL2U

5

30

55

83

108

 

 

 

 

 

 

PW9130G1000R-XL2U

7

29

51

81

98

PW9130i1000R-XL2U

 

 

 

 

 

PW9130G1000R-XL2UEU

 

 

 

 

 

PW9130G1000R-XL2UAU

 

 

 

 

 

 

 

 

 

 

 

PW9130L1500R-XL2U

5

23

48

67

91

 

 

 

 

 

 

PW9130i1500R-XL2U

5

24

44

72

89

PW9130G1500R-XL2UAU

 

 

 

 

 

 

 

 

 

 

 

PW9130L2000R-XL2U

6

33

59

88

112

 

 

 

 

 

 

PW9130G2000R-XL2U

6

33

59

88

119

PW9130i2000R-XL2U

 

 

 

 

 

PW9130G2000R-XL2UEU

 

 

 

 

 

PW9130G2000R-XL2UAU

 

 

 

 

 

 

 

 

 

 

 

PW9130L2500R-XL2U

4

26

47

71

95

PW9130G2500R-XL2U

 

 

 

 

 

PW9130G2500R-XL2UEU

 

 

 

 

 

 

 

 

 

 

 

PW9130L3000R-XL2U

3

20

36

53

71

 

 

 

 

 

 

PW9130G3000R-XL2U

3

18

34

53

69

PW9130i3000R-XL2U

 

 

 

 

 

PW9130G3000R-XL2UEU

 

 

 

 

 

PW9130G3000R-XL2UAU

 

 

 

 

 

 

 

 

 

 

 

NOTE Battery times are approximate and vary depending on the load configuration and battery charge.

88

Eaton® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com

Page 96
Image 96
Eaton Electrical 9130 manual Battery Runtimes in Minutes at 100% Load Rack Models