UPS MAINTENANCE

5.Carefully pull the handle on the battery tray and slide the battery package slowly out onto a flat, stable surface; use two hands to support the battery package. See “Recycling the Used Battery or UPS” on page 73 for proper disposal.

NOTE Verify that the replacement batteries have the same rating as the batteries being replaced.

6.Slide the new battery package into the cabinet. Push the battery package in firmly.

7.Replace the battery cover plate onto the screw mounts, threading the battery connector through the access slot.

C A U T I O N

A small amount of arcing may occur when connecting the internal batteries. This is normal and will not harm personnel. Connect the cables quickly and firmly.

8.Reconnect the internal battery connector. Connect red to red, and black to black. Press the two parts tightly together to ensure a proper connection.

9.Up to 1500 VA models only. If the EBM cable is not connected to an EBM, clip the EBM cable back into its holder on the battery cover plate. See Figure 24.

10.Replace the UPS right front cover.

To replace the cover, verify that the ribbon cable is protected and (if EBMs are installed) the EBM cable is routed through the knockout on the bottom of the cover. Slide the cover to the left until it aligns with the left front cover. Reinstall the two screws on the right side of the right front cover.

11.Continue to “Testing New Batteries” on page 72.