COMMUNICATION

Programmable Signal Inputs

The UPS incorporates four programmable signal inputs: one RS-232 input, two connectivity card inputs, and one REPO terminal input. See Figure 18 on page 53 for the locations of the ports. Configure the inputs with the “Signal Inputs” setting in “User Settings” on page 40.

Table 6 shows the programmable settings for the signal inputs. Table 7 shows the operation logic for the signal inputs.

Table 6. Programmable Signal Inputs

Signal

Description

 

 

Not Used

The input operates only as a serial input (RxD) or has no function.

 

 

Force Bypass

If active, the UPS is forced to static bypass operation regardless of

 

the bypass status.

 

 

Remote Shutdown

If active, the UPS output turns off after a user-defined remote

 

shutdown delay. The batteries continue charging. Inactive input

 

does not abort the shutdown countdown and does not cause the

 

UPS to start up automatically.

 

 

Delayed

If active, the UPS output turns off after a user-defined delayed

Shutdown

shutdown delay. The batteries continue charging. Inactive input

(and restart)

does not abort the shutdown countdown but will cause the UPS to

 

start up automatically if the input voltage exists.

 

 

On Generator

If active, synchronization is disabled and the UPS transfers to

 

bypass.

 

 

Building Alarm 1

If active, the UPS generates the “Building Alarm 1” alarm.

 

 

Table 7. Polarity Options

Input

Description

 

 

High

Active state on high voltage (+Udc) level

 

 

Low

Active state on low voltage (GND or -Udc) level

 

 

Eaton® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com

59

Page 67
Image 67
Eaton Electrical 9130 manual Programmable Signal Inputs, Polarity Options, Input Description