Table 16. Electrical Input (Tower Models)

Model

Default Input

Selectable Input

Voltage Range

(Voltage/Current)

Voltages

at 100% Load

 

 

 

 

 

PW9130L700T-XL

120V / 5.8A

100*, 110**, 120, 127

80–138 Vac

 

 

 

 

PW9130L1000T-XL

120V / 8.3A

100*, 110**, 120, 127

80–138 Vac

 

 

 

 

PW9130L1500T-XL

120V / 12.5A

100*, 110**, 120, 127

80–138 Vac

 

 

 

 

PW9130L2000T-XL

120V / 16.7A

100*, 110**, 120, 127

90–138 Vac

 

 

 

 

PW9130L3000T-XL

120V / 25.0A

100*, 110**, 120, 127

90–138 Vac

 

 

 

 

PW9130G1000T-XL

208V / 4.4A

200*, 208**, 220, 230, 240

160–276 Vac

 

 

 

 

PW9130G2000T-XL

208V / 8.7A

200*, 208**, 220, 230, 240

180–276 Vac

 

 

 

 

PW9130G3000T-XL

208V / 13.0A

200*, 208**, 220, 230, 240

180–276 Vac

 

 

 

 

PW9130i700T-XL

230V / 3.0A

200*, 208**, 220, 230, 240

160–276 Vac

 

 

 

 

PW9130i1000T-XL

230V / 4.3A

200*, 208**, 220, 230, 240

160–276 Vac

 

 

 

 

PW9130i1500T-XL

230V / 6.5A

200*, 208**, 220, 230, 240

160–276 Vac

 

 

 

 

PW9130i2000T-XL

230V / 8.7A

200*, 208**, 220, 230, 240

180–276 Vac

 

 

 

 

PW9130i3000T-XL

230V / 13.0A

200*, 208**, 220, 230, 240

180–276 Vac

 

 

 

 

PW9130G1000T-XLEU

208V / 4.4A

200*, 208**, 220, 230, 240

180–276 Vac

 

 

 

 

PW9130G2000T-XLEU

208V / 8.7A

200*, 208**, 220, 230, 240

180–276 Vac

 

 

 

 

PW9130G3000T-XLEU

208V / 13.0A

200*, 208**, 220, 230, 240

180–276 Vac

 

 

 

 

PW9130G700T-XLAU

240V / 4.2A

200*, 208**, 220, 230, 240

160–276 Vac

 

 

 

 

PW9130G1000T-XLAU

240V / 4.2A

200*, 208**, 220, 230, 240

160–276 Vac

 

 

 

 

PW9130G1500T-XLAU

240V / 6.25A

200*, 208**, 220, 230, 240

160–276 Vac

 

 

 

 

PW9130G2000T-XLAU

240V / 8.3A

200*, 208**, 220, 230, 240

180–276 Vac

 

 

 

 

PW9130G3000T-XLAU

240V / 12.5A

200*, 208**, 220, 230, 240

180–276 Vac

 

 

 

 

*100V and 200V are derated by 20%. ** 110V and 208V are derated by 10%.