TROUBLESHOOTING

To check the Event Log for a history of conditions:

1.Press any button on the front panel display to activate the menu options.

2.Press the

button until EVENT LOG displays.

3.Press the Enter button to display the list of conditions.

You can also retrieve the entire Event Log in ASCII format. See “Retrieving the Event Log” on page 47.

The following table describes typical alarms and conditions.

Alarm or Condition

Possible Cause

Action

 

 

 

On Battery

A utility failure has occurred and

 

 

 

 

 

the UPS is in Battery mode.

LED is on.

1 beep every 5 seconds.

The UPS is powering the equipment with battery power. Prepare your equipment for shutdown.

Battery Low

The UPS is in Battery mode and

This warning is approximate, and the actual time to

 

the battery is running low.

shutdown may vary significantly. Depending on the

 

 

UPS load and number of Extended Battery Modules

LED is flashing slowly.

 

(EBMs), the “Battery Low” warning may occur

 

before the batteries reach 25% capacity. See

 

 

1 beep every second.

 

Table 23 on page 88 for estimated runtimes.

 

 

 

On Bypass

The UPS is in Bypass mode.

The equipment transferred to bypass utility power.

 

 

Battery mode is not available and your equipment

 

 

is not protected; however, the utility power

LED is on.

 

continues to be passively filtered by the UPS.

 

Check for one of the following alarms:

 

 

1 beep every 5 seconds.

 

overtemperature, overload, or UPS failure.

 

 

 

On Bypass

The UPS is on bypass while

The equipment transferred to bypass utility power

 

operating on the High Efficiency

as a normal function of High Efficiency operation.

 

setting.

Battery mode is available and your equipment is

LED is on.

 

protected.

 

 

No beeping.

 

 

 

 

 

Batteries Disconnected

The UPS does not recognize the

If the condition persists, contact your service

 

internal batteries.

representative.

 

 

 

 

The batteries are disconnected.

Verify that all batteries are properly connected. If

LED is on.

 

the condition persists, contact your service

1 beep every second.

 

representative.

 

 

 

102

Eaton® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com

Page 110
Image 110
Eaton Electrical 9130 manual Alarm or Condition Possible Cause Action, Battery is running low