OPERATION

ÊConfiguring Battery Settings

Set the UPS for the number of EBMs installed, whether to run automatic battery tests, and automatic restart configuration.

Configuring the UPS for EBMs

To ensure maximum battery runtime, configure the UPS for the correct number of EBMs:

1.Press any button on the front panel display to activate the menu options, then select SETTINGS, USER SETTINGS, and NUMBER OF BATTERY STRINGS.

2. Use the or buttons to select the number of battery strings according to your UPS configuration:

All UPS and EBM Cabinets

Number of Battery Strings

 

 

UPS only (internal batteries)

1 (default)

 

 

UPS + 1 EBM

3

 

 

UPS + 2 EBMs

5

 

 

UPS + 3 EBMs

7

 

 

UPS + 4 EBMs

9

 

 

NOTE If 0 is selected, no batteries are connected and all battery-related alarms are disabled.

NOTE The UPS contains one battery string; each EBM contains two battery strings.

3.Press the button to save the setting.

4.Press the ESC button until the start screen appears.