SPECIFICATIONS
Eaton® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com
80
Table 15. Electrical Input (Rackmount Models)
Model Default Input
(Voltage/Current) Selectable Input
Voltages Voltage Range
at 100% Load
PW9130L700R-XL2U 120V / 5.8A 100*, 110**, 120, 127 80–138 Vac
PW9130L1000R-XL2U 120V / 8.3A 100*, 110**, 120, 127 80–138 Vac
PW9130L1500R-XL2U 120V / 12.5A 100*, 110**, 120, 127 80–138 Vac
PW9130L2000R-XL2U 120V / 16.7A 100*, 110**, 120, 127 90–138 Vac
PW9130L2500R-XL2U 120V / 20.8A 100*, 110**, 120, 127 90–138 Vac
PW9130L3000R-XL2U 120V / 25A 100*, 110**, 120, 127 90–138 Vac
PW9130G1000R-XL2U 208V / 4.8A 200*, 208**, 220, 230, 240 160–276 Vac
PW9130G2000R-XL2U 208V / 9.6A 200*, 208**, 220, 230, 240 180–276 Vac
PW9130G2500R-XL2U 208V / 12A 200*, 208**, 220, 230, 240 180–276 Vac
PW9130G3000R-XL2U 208V / 14.4A 200*, 208**, 220, 230, 240 180–276 Vac
PW9130i1000R-XL2U 230V / 4.3A 200*, 208**, 220, 230, 240 160–276 Vac
PW9130i1500R-XL2U 230V / 6.5A 200*, 208**, 220, 230, 240 160–276 Vac
PW9130i2000R-XL2U 230V / 8.7A 200*, 208**, 220, 230, 240 180–276 Vac
PW9130i3000R-XL2U 230V / 13.0A 200*, 208**, 220, 230, 240 180–276 Vac
PW9130G1000R-XL2UEU 208V / 4.8A 200*, 208**, 220, 230, 240 180–276 Vac
PW9130G2000R-XL2UEU 208V / 9.6A 200*, 208**, 220, 230, 240 180–276 Vac
PW9130G2500R-XL2UEU 208V / 12A 200*, 208**, 220, 230, 240 180–276 Vac
PW9130G3000R-XL2UEU 208V / 14.4A 200*, 208**, 220, 230, 240 180–276 Vac
PW9130G1000R-XL2UAU 240V / 4.4A 200*, 208**, 220, 230, 240 160–276 Vac
PW9130G1500R-XL2UAU 240V / 6.25A 200*, 208**, 220, 230, 240 160–276 Vac
PW9130G2000R-XL2UAU 240V / 8.7A 200*, 208**, 220, 230, 240 180–276 Vac
PW9130G3000R-XL2UAU 240V / 13.0A 200*, 208**, 220, 230, 240 180–276 Vac
* 100V and 200V are derated by 20%.