SPECIFICATIONS

Table 25. Battery

 

Internal Batteries

EBMs

 

 

 

Rackmount

700–1000 VA models: 36 Vdc (3 12V, 9 Ah)

PW9130N1000R-EBM2U: 36 Vdc (2x3 12V, 9 Ah)

Configuration

1500 VA models: 48 Vdc (4 12V, 9 Ah)

PW9130N1500R-EBM2U: 48 Vdc (2x4 12V, 9 Ah)

 

2000–3000 VA models: 72 Vdc (6 12V, 9 Ah)

PW9130N3000R-EBM2U: 72 Vdc (2x6 12V, 9 Ah)

 

 

 

Tower

700 VA models: 24 Vdc (2 12V, 9 Ah)

PW9130N1000T-EBM: 36 Vdc (2x3 12V, 9 Ah)

Configuration

1000 VA models: 36 Vdc (3 12V, 9 Ah)

PW9130N1500T-EBM: 48 Vdc (2x4 12V, 9 Ah)

 

1500 VA models: 48 Vdc (4 12V, 9 Ah)

PW9130N3000T-EBM: 96 Vdc (2x8 12V, 9 Ah)

 

2000–3000 VA models: 96 Vdc (8 12V, 9 Ah)

 

 

 

 

Fuses

Not applicable

(4) 30A/125 Vdc fuses per EBM

 

 

Type

Sealed, maintenance-free, valve-regulated, lead-acid,

 

with minimum 3-year float service life at 25°C (77°F)

 

 

Monitoring

Advanced monitoring for earlier failure detection and warning

 

 

Recharge Time

Internal batteries: 3 hours

(to 90%)

1 EBM: 9 hours; 2 EBMs: 15 hours; 3 EBMs: 21 hours; 4 EBMs: 27 hours

 

 

Battery Port

External three-pole Anderson connector on UPS for connection to EBM

 

 

 

90

Eaton® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com

Page 98
Image 98
Eaton Electrical 9130 manual Battery, Internal Batteries EBMs