TROUBLESHOOTING

Alarm or Condition

Possible Cause

Action

 

 

 

Overload

Power requirements exceed the

Remove some of the equipment from the UPS. The

 

UPS capacity (greater than

UPS continues to operate, but may switch to

 

100% of nominal; see page 84 for

Bypass mode or shut down if the load increases.

LED is on.

specific output overload

The alarm resets when the condition becomes

ranges).

inactive.

1 beep every second.

 

 

 

 

 

Overtemperature

The UPS internal temperature is

If the UPS transferred to Bypass mode, the UPS will

 

too high or a fan has failed.

return to normal operation when the temperature

 

At the warning level, the UPS

drops 5°C below the warning level.

LED is on.

generates the alarm but remains

If the condition persists, shut down the UPS. Clear

1 beep every second.

in the current operating state.

vents and remove any heat sources. Allow the UPS

If the temperature rises another

to cool. Ensure the airflow around the UPS is not

 

 

10°C, the UPS transfers to

restricted. Restart the UPS.

 

Bypass mode or shuts down if

If the condition continues to persist, contact your

 

bypass is unusable.

service representative.

Battery Overvoltage

The UPS battery voltage is too

 

high.

LED is on.

1 beep every second.

The UPS turns off the charger until the next power recycle. Contact your service representative.

Site Wiring Fault

LED is on.

1 beep every second.

“L” Models Only. Ground wire

Have a qualified electrician correct the wiring.

connection does not exist, or the

 

line and neutral wires are

 

reversed in the wall outlet.

 

 

 

“G” Models Only. Input is phase

Disable the Site Wiring Fault Alarm setting (see

to phase (neutral is not bonded

“User Settings” on page 40).

to ground).

 

 

 

 

“i” and “G (AU)” Models Only.

Rotate the Schuko input connector.

 

The polarity of the UPS input

 

 

power cord connector is

 

 

incorrect.

 

 

 

 

 

“i” and “G (AU)” Models Only.

Have a qualified electrician correct the wiring. If

 

The ground wire connection

the UPS is installed to input supply without ground,

 

does not exist.

disable the “Site Wiring Fault Alarm” setting (see

 

 

“User Settings” on page 40).

 

 

 

The UPS does not provide

The batteries need charging or

Apply utility power for 48 hours to charge the

the expected backup time.

service.

batteries. If the condition persists, contact your

 

 

service representative.

 

 

 

Power is not available at the

The UPS is in Standby mode.

Supply power to the connected equipment: Press

UPS output receptacles.

 

the On/Off button for at least 1 second, until the

 

 

front panel displays “UPS starting...”.

 

 

 

Eaton® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com

103

Page 111
Image 111
Eaton Electrical 9130 manual LED is on Beep every second, Models Only. Ground wire