13
Reference Manual
00809-0100-4102, Rev AA
Section 2: Configuration
May 2013
Configuration

2.4.4 Set process variable units

The PV Unit command sets the process variable units to allow you to monitor your process using
the appropriate units of measure.
To select a unit of measure for the PV:
1. From the Home screen, select 2: Configure.
2. Select 2: Manual Setup.
3. Select 2: Pressure.
4. Select 3: Unit to select from the following engineering units:

2.4.5 Remove Power Module

After the sensor and network have been configured, remove the Power Module and replace the
housing cover. The Power Module should be inserted only when the device is ready to be
commissioned.
Use caution when handling the Power Module. The Power Module may be damaged if dropped
from heights in excess of 6.10 m (20 ft).
2.5 Configure for Pressure

2.5.1 Re-Mapping device variables

The re-mapping function allows the transmitter primary, secondary, tertiary, and quaternary
variables (PV, SV, TV, and QV) to be configured in one of two configurations. The user may select
either the option of Classic mapping or Scaled Variable Mapping, see Table 2- 1 for what is
mapped to each variable. All variables can be remapped with a Field Communicator or AMS
Device Manager.
Fast Keys 2, 2, 2, 3
inH2O at 4 °C mmH2O at 68 °F mmHg Mpa
inH2O at 60 °F cmH2O at 4 °C Psi Bar
inH2O at 68 °F mH2O at 4 °C Atm Mbar
ftH2O at 4 °C inHg at 0 °C Torr g/cm2
ftH2O at 60 °F mmHg at 0 °C Pascals kg/cm2
ftH2O at 68 °F cmHg at 0 °C hectoPascals kg/m2
mmH2O at 4 °C mHg at 0 °C Kilopascals