2.4.4Set process variable units

Fast Keys

2, 2, 2, 3

The PV Unit command sets the process variable units to allow you to monitor your process using the appropriate units of measure.

To select a unit of measure for the PV:

1.From the Home screen, select 2: Configure.

2.Select 2: Manual Setup.

3.Select 2: Pressure.

4.Select 3: Unit to select from the following engineering units:

inH2O at 4 °C

mmH2O at 68 °F

mmHg

inH2O at 60 °F

cmH2O at 4 °C

Psi

inH2O at 68 °F

mH2O at 4 °C

Atm

ftH2O at 4 °C

inHg at 0 °C

Torr

ftH2O at 60 °F

mmHg at 0 °C

Pascals

ftH2O at 68 °F

cmHg at 0 °C

hectoPascals

mmH2O at 4 °C

mHg at 0 °C

Kilopascals

Mpa

Bar

Mbar

g/cm2

kg/cm2

kg/m2

2.4.5Remove Power Module

After the sensor and network have been configured, remove the Power Module and replace the housing cover. The Power Module should be inserted only when the device is ready to be commissioned.

Use caution when handling the Power Module. The Power Module may be damaged if dropped from heights in excess of 6.10 m (20 ft).

2.5Configure for Pressure

2.5.1Re-Mapping device variables

The re-mapping function allows the transmitter primary, secondary, tertiary, and quaternary variables (PV, SV, TV, and QV) to be configured in one of two configurations. The user may select either the option of Classic mapping or Scaled Variable Mapping, see Table 2-1for what is mapped to each variable. All variables can be remapped with a Field Communicator or AMS Device Manager.